Ratio of vertical separation, 132 vs 220 kV

Short answer

Vertical separation Y = string length l + air clearance a. For 132 kV: l=1.614 m, a=1.585 m, Y=3.20 m. For 220 kV: l=2.344 m, a=2.539 m, Y=4.88 m. Ratio = 3.20/4.88 ≈ 0.66.

Compute ratio of vertical separation of conductors of 132 kV and 220 kV double circuit transmission line. Derive any expressions used.

The vertical separation between conductors is fixed by the insulator string length ll plus the minimum air clearance aa.

Derivation of the expressions

1. Minimum air clearance. As given with IOE papers, allow 6.5 inch per 10 kV of the maximum phase voltage (rms), plus 8 inch as a factor of safety:

a=(6.5×Vmax/310+8) incha = \left(6.5\times\frac{V_{max}/\sqrt3}{10} + 8\right)\ \text{inch}

2. String length. l=n×146l = n\times 146 mm plus about 0.3 m of hardware, where nn is the number of 254 × 146 mm discs.

3. Vertical spacing. Take a double-circuit tower with conductors arranged vertically. The upper conductor hangs a distance ll below its cross arm, and it lies directly above the tip of the next cross arm, which is YY below.

  ======o  upper cross arm
        |  l (string)
        *  upper conductor
        :  >= a (air clearance)
  ======o  lower cross arm
        |  l
        *  lower conductor

The gap between the upper conductor and the lower cross arm is Y−lY - l, and it must be at least aa:

Y−l≥a  ⇒  Y=l+aY - l \ge a \;\Rightarrow\; Y = l + a

When the string swings by θ, the conductor rises: its vertical distance from the cross arm above becomes lcos⁡θl\cos\theta. That only increases the gap, so the unswung position governs.

132 kV double circuit

  • Maximum system voltage 145 kV, so the phase voltage is 145/3=83.72145/\sqrt3 = 83.72 kV.
  • a=6.5×8.372+8=62.42a = 6.5\times8.372+8 = 62.42 inch =1.585= 1.585 m.
  • Discs: 9 discs, the standard practice for 132 kV. This covers the table check (1-min wet withstand 230 kV needs 6 discs; impulse 550 kV needs 7 discs) plus a margin for switching surges, pollution and one defective disc.
  • l=9×0.146+0.3=1.614l = 9\times0.146+0.3 = 1.614 m.
  • Y132=1.614+1.585=3.199Y_{132} = 1.614+1.585 = 3.199 m.

220 kV double circuit

  • Maximum system voltage 245 kV, so the phase voltage is 141.45 kV.
  • a=6.5×14.145+8=99.94a = 6.5\times14.145+8 = 99.94 inch =2.539= 2.539 m.
  • Discs: 14, the standard 220 kV suspension string.
  • l=14×0.146+0.3=2.344l = 14\times0.146+0.3 = 2.344 m.
  • Y220=2.344+2.539=4.883Y_{220} = 2.344+2.539 = 4.883 m.

Ratio

Y132Y220=3.1994.883=0.655\frac{Y_{132}}{Y_{220}} = \frac{3.199}{4.883} = 0.655

Answer: the vertical separation is about 3.2 m for 132 kV and 4.9 m for 220 kV, a ratio of about 0.66 : 1. The 132 kV spacing is roughly two-thirds of the 220 kV spacing, because both the clearance and the string length grow with voltage.

✓ Answer checked by Claude Opus 5.5 (high effort)