- Asked 2/20
- 2079 Chaitra · 8 marks
Tower dimensions for 220 kV single circuit line
Short answer
Using a 2.54 m air clearance and 2.0 m insulator string (11 discs): cross-arm length 4.0 m; vertical conductor separation4.6 m; horizontal separation9.5 m; one earth wire; earth wire height above top conductor8.3 m.
For a 220 kV single circuit transmission line, suggest the dimensions for following: (i) Cross arm length (ii) Insulator string length (iii) Horizontal and vertical separation of conductors (iv) Number of earth wires (v) Height of earth wire from the top most conductor. (Take maximum swing of insulator as: 45°)
The tower dimensions follow from the minimum air clearance, the insulator string length and the 45° swing. They are taken from the given appendix rules and common IS practice.
Data assumed: maximum system voltage kV. Tower width at cross-arm level is 1.5 m. Discs are 254 × 154 mm.
Minimum air clearance
Using 6.5 inch per 10 kV of maximum phase rms voltage plus 8 inch:
As a check, 1 cm per kV of phase peak voltage plus 30 cm gives cm. The larger value, m, is used.
(ii) Insulator string length
For 220 kV, 10 discs meet the wet (395 kV) and impulse (900 kV) withstand levels. One spare disc is added, giving 11 discs:
(i) Cross-arm length
When the string swings by , the conductor must stay at least from the tower:
Take 4.0 m from the tower face.
(iii) Conductor separation
- Vertical (between cross-arms): the conductor hanging from the upper arm must keep clearance from the arm below.
- Horizontal (conductors on opposite sides of the tower):
This is well above the phase-to-phase clearance (about m).
(iv) Number of earth wires
A 220 kV single-circuit line in a vertical or delta configuration is narrow enough for one earth wire at the peak to give a 30° shielding angle.
(v) Height of earth wire above the top conductor
For a shielding angle , the horizontal distance from the tower centre to the outermost conductor is m. So:
| Item | Value |
|---|---|
| Air clearance | 2.54 m |
| String length | 2.0 m (11 discs) |
| Cross-arm length | 4.0 m |
| Vertical spacing | 4.6 m |
| Horizontal spacing | 9.5 m |
| Earth wires | 1 |
| Earth wire above top conductor | 8.3 m |
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Tower dimensions for 220 kV double circuit line · Transmission and Distribution System Design, chapter 4 · asked 2×
- Air clearances for 220 kV double circuit line · Transmission and Distribution System Design, chapter 4
- Air clearances, 220 kV line for 200 MW · Transmission and Distribution System Design, chapter 4
- Number of insulator discs for 220 kV line · Transmission and Distribution System Design, chapter 3
- 400 kV lines: configuration, V-string, earth wires · Transmission and Distribution System Design, chapter 4
- Air clearances for 132 kV double circuit line · Transmission and Distribution System Design, chapter 4
- Ratio of vertical separation, 132 vs 220 kV · Transmission and Distribution System Design, chapter 4
- Tower top potential and insulator string voltage · High Voltage Engineering, chapter 3 · asked 2×
- True/false: cross-arm length and string efficiency · High Voltage Engineering, chapter 5
All Transmission and Distribution System Design chapter 4 questions →