Tower top potential and insulator string voltage
Short answer
(i) Using parallel impedances: (a) all cases Zeq=31.75 Ω, Vt=1587.3 kV; (b) footing only, Vt=2000 kV; (c) one ground wire Zeq=33.90 Ω, Vt=1694.9 kV. (ii) Insulator voltage = (1−0.2)×1587.3=1269.8 kV.
A tower of a 735 kV line has a 40-ohm footing resistance and two ground wires each with Zg = 500 ohms. The lightning stroke surge impedance is Zs = 400 ohm. For Is = 50 kA, crest, calculate (i) the tower top potential (a) considering all impedances, (b) neglecting the ground wire and stroke surge impedances and (c) considering only one ground wire and stroke surge impedance (ii) the voltage experienced by the insulator string in case (a) of above if the coupling factor between the line and ground conductors is 0.2.
When lightning strikes the tower top, the stroke current divides between all the paths that meet at the tower top. These paths are in parallel: the stroke channel itself (surge impedance ), the tower footing resistance , and the ground wires (surge impedance each). So the tower-top potential is
where is the number of ground wires. (Tower inductance and travel time in the tower are neglected.)
Data: , (each), , kA.
(i)(a) Considering all impedances (two ground wires)
(i)(b) Neglecting ground wires and stroke impedance
Only the footing resistance carries the current:
(i)(c) One ground wire and stroke impedance
| Case | () | (kV) |
|---|---|---|
| (a) all impedances | 31.75 | 1587.3 |
| (b) footing R only | 40.00 | 2000.0 |
| (c) one ground wire | 33.90 | 1694.9 |
The ground wires and the stroke channel take part of the current, so they lower the tower-top potential. The footing resistance is the largest single factor.
(ii) Voltage across the insulator string, case (a)
The surge on the ground wire induces a voltage on the phase conductor through the coupling factor . The conductor rises with the tower, so the insulator string sees only the difference:
If this exceeds the flashover voltage of the string, a back-flashover occurs from the tower (at high potential) to the conductor.
Answer: = 1587.3 kV (a), 2000 kV (b), 1694.9 kV (c); insulator string voltage in case (a) = 1269.8 kV.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Tower top potential for lightning stroke · High Voltage Engineering, chapter 3 · asked 2×
- Tower top potential and discs against back-flashover · High Voltage Engineering, chapter 3
- Direct lightning stroke overvoltage and tower footing · High Voltage Engineering, chapter 3
- Transformer BIL and arrester resistance for 500 kV line · High Voltage Engineering, chapter 4
- Surge impedance and velocity of 220 kV line · High Voltage Engineering, chapter 3 · asked 2×