Short answer

(a) With all impedances: Zeq=31.75 Ω, Vt=1587.3 kV. (b) Footing only: Vt=2000 kV. (c) One ground wire: Zeq=33.90 Ω, Vt=1694.9 kV.

A tower of a 735 kV line has a 40-ohm footing resistance and two ground wires each with Zg = 500 ohms. The lightning stroke surge impedance is Zs = 400 ohm. For Is = 50 kA, crest, calculate (i) the tower top potential (a) considering all impedances, (b) neglecting the ground wire and stroke surge impedances, and (c) considering only one ground wire and stroke surge impedance.

When lightning strikes the tower top, the stroke current IsI_s divides between all the paths that meet at the tower top. These paths are in parallel: the stroke channel itself (surge impedance ZsZ_s), the tower footing resistance RR, and the ground wires (surge impedance ZgZ_g each). So the tower-top potential is

Vt=IsZeq,1Zeq=1Zs+1R+nZgV_t = I_s Z_{eq}, \qquad \frac{1}{Z_{eq}} = \frac{1}{Z_s} + \frac{1}{R} + \frac{n}{Z_g}

where nn is the number of ground wires. (Tower inductance and travel time in the tower are neglected.)

Data: R=40 ΩR = 40\ \Omega, Zg=500 ΩZ_g = 500\ \Omega (each), Zs=400 ΩZ_s = 400\ \Omega, Is=50I_s = 50 kA.

(i)(a) Considering all impedances (two ground wires)

1Zeq=1400+140+2500=0.0025+0.025+0.004=0.0315 SZeq=31.75 ΩVt=50×31.75=1587.3 kV\begin{aligned} \frac{1}{Z_{eq}} &= \frac{1}{400} + \frac{1}{40} + \frac{2}{500} \\ &= 0.0025 + 0.025 + 0.004 = 0.0315\ \text{S} \\ Z_{eq} &= 31.75\ \Omega \\ V_t &= 50 \times 31.75 = 1587.3\ \text{kV} \end{aligned}

(i)(b) Neglecting ground wires and stroke impedance

Only the footing resistance carries the current:

Vt=IsR=50×40=2000 kVV_t = I_s R = 50 \times 40 = 2000\ \text{kV}

(i)(c) One ground wire and stroke impedance

1Zeq=1400+140+1500=0.0295 SZeq=33.90 ΩVt=50×33.90=1694.9 kV\begin{aligned} \frac{1}{Z_{eq}} &= \frac{1}{400} + \frac{1}{40} + \frac{1}{500} = 0.0295\ \text{S} \\ Z_{eq} &= 33.90\ \Omega \\ V_t &= 50 \times 33.90 = 1694.9\ \text{kV} \end{aligned}
CaseZeqZ_{eq} (Ω\Omega)VtV_t (kV)
(a) all impedances31.751587.3
(b) footing R only40.002000.0
(c) one ground wire33.901694.9

The ground wires and the stroke channel take part of the current, so they lower the tower-top potential. The footing resistance is the largest single factor.

Answer: (a) 1587.3 kV, (b) 2000 kV, (c) 1694.9 kV.