Direct lightning stroke overvoltage and tower footing

Short answer

Direct stroke on conductor: V=I·Z0/2. On ground wire: Vg=I·Zg/2, gap voltage=(1‑K)Vg. On tower: Vt≈I·Rf, insulator stress=(1‑K)Vt. Low footing resistance (≤10 Ω) limits back‑flashover and ensures negative reflections, protecting insulation.

Describe the expression for over-voltage due to lightning when a direct stroke falls on a power conductor, earth wire and on the tower. And hence discuss the importance of Tower footing resistance in the resulting overvoltage.

A direct stroke delivers a lightning current II straight onto a line component. The voltage produced depends on the surge impedance seen from the point of strike.

1. Stroke on a phase conductor

The current divides equally into the two directions of the conductor, each of surge impedance Z0Z_0:

V=I⋅Z02V = I \cdot \frac{Z_0}{2}

For example, I=10I = 10 kA and Z0=400 ΩZ_0 = 400\ \Omega give V=2000V = 2000 kV. This is far above the insulation level of most lines, so a direct stroke to an unshielded phase conductor almost always causes flashover. This is why ground wires are used.

2. Stroke on the earth (ground) wire at mid-span

The current divides both ways along the ground wire (surge impedance ZgZ_g):

Vg=IZg2V_g = I\frac{Z_g}{2}

The phase conductor gets an induced voltage KVgKV_g through the coupling factor KK. The voltage across the air gap between ground wire and conductor at mid-span is

Vgap=(1−K)Vg=(1−K)IZg2V_{gap} = (1 - K)V_g = (1-K)\frac{I Z_g}{2}

The waves travel to the adjacent towers and are reflected negatively there by the low tower footing resistance. So the mid-span voltage is limited if the span is short and the clearance is adequate.

3. Stroke on the tower top

The current divides between the stroke channel ZsZ_s, the ground wires ZgZ_g and the tower footing resistance RR:

Vt=I Zeq,1Zeq=1Zs+1R+nZgV_t = I\,Z_{eq}, \qquad \frac{1}{Z_{eq}} = \frac{1}{Z_s} + \frac{1}{R} + \frac{n}{Z_g}

If the ground wires and stroke impedance are neglected, Vt≈IRV_t \approx IR. The insulator string then sees

Vins=(1−K)VtV_{ins} = (1 - K)V_t
     I (stroke)
       |
   ----+---- ground wire Zg  (both sides)
       |
     tower --- insulator --- phase conductor
       |
       R  footing
      gnd

Importance of tower footing resistance

  • VtV_t is roughly proportional to RR. With R=40 ΩR = 40\ \Omega and I=50I = 50 kA, VtV_t can be as high as 2000 kV. With R=10 ΩR = 10\ \Omega it falls to 500 kV or less.
  • If (1−K)Vt(1-K)V_t exceeds the impulse flashover voltage of the insulator string, a back-flashover occurs: the tower, at high potential, flashes over to the phase conductor. The ground wire then fails to protect the line.
  • Low footing resistance also sends a strong negative reflection back up the tower, which cuts the tower-top voltage quickly.
  • Practice: keep RR below about 10 Ω (and preferably below 5 Ω on EHV lines). Use extra earth rods, counterpoise wires buried along the line, and chemical earthing in high-resistivity soil.

So shielding with ground wires protects the conductor only when the footing resistance is low. A high RR turns a shielded stroke into a back-flashover.