Direct lightning stroke overvoltage and tower footing
Short answer
Direct stroke on conductor: V=I·Z0/2. On ground wire: Vg=I·Zg/2, gap voltage=(1‑K)Vg. On tower: Vt≈I·Rf, insulator stress=(1‑K)Vt. Low footing resistance (≤10 Ω) limits back‑flashover and ensures negative reflections, protecting insulation.
Describe the expression for over-voltage due to lightning when a direct stroke falls on a power conductor, earth wire and on the tower. And hence discuss the importance of Tower footing resistance in the resulting overvoltage.
A direct stroke delivers a lightning current straight onto a line component. The voltage produced depends on the surge impedance seen from the point of strike.
1. Stroke on a phase conductor
The current divides equally into the two directions of the conductor, each of surge impedance :
For example, kA and give kV. This is far above the insulation level of most lines, so a direct stroke to an unshielded phase conductor almost always causes flashover. This is why ground wires are used.
2. Stroke on the earth (ground) wire at mid-span
The current divides both ways along the ground wire (surge impedance ):
The phase conductor gets an induced voltage through the coupling factor . The voltage across the air gap between ground wire and conductor at mid-span is
The waves travel to the adjacent towers and are reflected negatively there by the low tower footing resistance. So the mid-span voltage is limited if the span is short and the clearance is adequate.
3. Stroke on the tower top
The current divides between the stroke channel , the ground wires and the tower footing resistance :
If the ground wires and stroke impedance are neglected, . The insulator string then sees
I (stroke)
|
----+---- ground wire Zg (both sides)
|
tower --- insulator --- phase conductor
|
R footing
gnd
Importance of tower footing resistance
- is roughly proportional to . With and kA, can be as high as 2000 kV. With it falls to 500 kV or less.
- If exceeds the impulse flashover voltage of the insulator string, a back-flashover occurs: the tower, at high potential, flashes over to the phase conductor. The ground wire then fails to protect the line.
- Low footing resistance also sends a strong negative reflection back up the tower, which cuts the tower-top voltage quickly.
- Practice: keep below about 10 Ω (and preferably below 5 Ω on EHV lines). Use extra earth rods, counterpoise wires buried along the line, and chemical earthing in high-resistivity soil.
So shielding with ground wires protects the conductor only when the footing resistance is low. A high turns a shielded stroke into a back-flashover.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Tower top potential for lightning stroke · High Voltage Engineering, chapter 3 · asked 2×
- Tower footing resistance of 20 Ω electrode design · High Voltage Engineering, chapter 2 · asked 3×
- Tower footing resistance of 16 Ω electrode design · High Voltage Engineering, chapter 2 · asked 3×
- Tower top potential and insulator string voltage · High Voltage Engineering, chapter 3 · asked 2×
- Overvoltage due to chopping of magnetising current · High Voltage Engineering, chapter 3
- Tower top potential and discs against back-flashover · High Voltage Engineering, chapter 3
- Earth resistance factors and lightning arrester earthing · Industrial Power Distribution and Illumination, chapter 2
- T/F: earth wire choice depends on circuit and voltage · Transmission and Distribution System Design, chapter 3
- T/F: lightning overvoltage in distribution system · Transmission and Distribution System Design, chapter 3
- Conductor volume vs voltage and power factor · Power System Analysis I, chapter 1