- Asked 3/20
- 2072 Magh · 8 marks
Tower footing resistance of 16 Ω electrode design
Short answer
Using R=ρ/(2πr) for hemisphere, R=(ρ/(2πL))ln(2L/a) for driven rod, and the counterpoise formula with R=16 Ω, ρ=100 Ω-m, a=1.25 cm and y=0.6 m gives: hemisphere radius 0.995 m, driven rod length 6.98 m, and counterpoise length 7.60 m buried 0.6 m deep.
It is necessary to obtain a tower footing resistance of 16 Ω in a soil of resistivity ρs = 100 Ω-m using the three common types of electrodes. Calculate the required dimensions if the radius of rod and counterpoise is 1.25 cm and depth of counterpoise is 0.6 m.
The three common electrodes are a hemisphere, a driven rod and a counterpoise. Using the standard relations (Begamudre, EHV AC Transmission Engineering):
Given: , , m, m.
(a) Hemisphere
(b) Driven rod
| (m) | () |
|---|---|
| 5.0 | 21.28 |
| 6.0 | 18.22 |
| 7.0 | 15.96 |
| 6.98 | 16.00 |
(c) Counterpoise
| (m) | () |
|---|---|
| 7.0 | 17.00 |
| 8.0 | 15.41 |
| 7.60 | 16.00 |
Answer: hemisphere radius = 0.995 m; driven rod length = 6.98 m; counterpoise length = 7.60 m (buried 0.6 m deep).
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Tower footing resistance of 20 Ω electrode design · High Voltage Engineering, chapter 2 · asked 3×
- Soil resistivity and reducing earth resistance · Switchgear and Protection, chapter 5