Tower footing resistance of 20 Ω electrode design
Short answer
Using resistance formulas: hemisphere R = ρ/(2πr) gives r = 0.796 m; rod R = (ρ/(2πL)) ln(2L/a) solved by trial yields L = 5.38 m; counterpoise R = (ρ/(πL))[ln(2L/√(2ay)) – 1] yields L = 5.80 m at depth 0.5 m.
It is necessary to obtain a tower-footing resistance of 20 Ω in a soil of resistivity ρs = 100 Ω-m using the most common three types of electrodes. Take a = 1.25 cm for rods and counterpoises and a depth y = 0.5 m for counterpoise. Calculate the required dimensions.
The three common footing electrodes are a hemisphere, a single driven rod and a counterpoise (buried horizontal wire). Their resistances (Begamudre, EHV AC Transmission Engineering) are:
Given: , , m, m.
(a) Hemisphere
(b) Driven rod
This is solved by trial:
| (m) | () |
|---|---|
| 4.0 | 25.71 |
| 5.0 | 21.28 |
| 5.38 | 20.00 |
(c) Counterpoise
| (m) | () |
|---|---|
| 5.0 | 22.24 |
| 6.0 | 19.50 |
| 5.80 | 20.00 |
Answer: hemisphere radius = 0.796 m; driven rod length = 5.38 m; counterpoise length = 5.80 m (at 0.5 m depth).
In practice the rod or counterpoise is preferred, since a 0.8 m radius hemisphere is hard to make; in high-resistivity soil several rods or longer counterpoises are used in parallel.