Earth resistance factors and lightning arrester earthing

Short answer

Soil type, moisture, dissolved salts, temperature, electrode size/depth, number/spacing, and contact condition affect earth resistance. For lightning arresters, a short straight copper/GI earth lead connects to a separate low-resistance (≈1–10 Ω) earth pit near the arrester, bonded to the station earth grid to equalize potential during surges.

What are the factors affecting the earth resistance? Explain briefly the earthing process for lightning arrester.

Factors affecting earth resistance

  1. Soil type: clay and loam have low resistivity; sand, gravel and rock have high resistivity.
  2. Moisture content: more moisture means much lower resistivity. Dry soil can have very high resistance, so resistance is worst in the dry season.
  3. Dissolved salts: salts in the soil water make it conductive. Salt, charcoal or bentonite added around the electrode lower resistance.
  4. Temperature: resistivity rises as temperature falls, very sharply below freezing.
  5. Electrode size and shape: larger plates and longer rods have lower resistance; length is more effective than diameter.
  6. Depth of electrode: deeper electrodes reach moist and stable soil.
  7. Number and spacing of electrodes: parallel electrodes reduce resistance if spaced well apart (≥ about twice their length).
  8. Contact with soil and condition of electrode: poor compaction, corrosion and loose joints raise resistance.

Earthing of a lightning arrester

A lightning arrester (surge arrester) must send a very high, very fast surge current (several kA) to earth with the smallest possible voltage rise. Its earthing is therefore done as follows:

 Line ──┬───────────── to transformer
        |
      [LA]
        |  short, straight earth lead
        |  (copper / GI strip)
        └───┐
  ground ───┼──────────────
           [E] separate LA earth pit
            |   (pipe or rod, low R)
            └── bonded to station earth
                  grid / transformer body
  1. Short and straight earth lead: the lead from the arrester's earth terminal to the electrode is as short and straight as possible, without sharp bends or loops. The inductance of a long lead adds an L·di/dt voltage to the arrester's residual voltage and reduces protection.
  2. Separate earth electrode: each arrester (or set of three) has its own earth pit (pipe/rod electrode) near the arrester, separate from the transformer neutral and body earth pits. Some utilities provide two LA earth pits at a distribution transformer.
  3. Low earth resistance: the LA earth resistance is kept low (in the order of 1–10 Ω, lower in substations), using chemical treatment or several electrodes where needed.
  4. Interconnection (bonding): the arrester earth is bonded to the transformer tank and the station earth grid. This keeps the equipment and the arrester at the same potential during a surge, so the insulation sees only the arrester's residual voltage.
  5. Conductor size: copper or GI strip/wire of adequate cross-section (for example 25 × 3 mm GI strip or 8 SWG GI wire, as per practice) to carry the surge and fault current, protected from mechanical damage.
  6. Placement: the arrester is mounted as close as possible to the equipment it protects (transformer bushings).
  7. Testing: the earth resistance of LA pits is checked periodically, especially before the monsoon (lightning season).

✓ Answer checked by Claude Opus 5.5 (high effort)