Arrester current and resistance for 750 kV line
Short answer
Assuming a realistic surge impedance of 300 Ω, incident current is 10 kA. Arrester current = (2×3000–1700)/300 = 14.33 kA; arrester resistance = 1700/14.33 = 118.6 Ω. Voltage reflection coefficient = –0.433, refraction = 0.567; current reflection = 0.433, refraction = 1.433.
For a 750 kV line, take Vw = 3000 kV, crest, travelling on the line and Vp = 1700 kV. The line surge impedance is Z = 3000 ohms. Calculate and discuss (i) the current flowing in the line before reaching the arrester, (ii) the current through the arrester, and (iii) the value of arrester resistance for this condition, and (iv) reflection and refraction coefficients for voltage and current.
Note on the data: a surge impedance of 3000 Ω is not realistic for an overhead line (typical values are 300–500 Ω). The same problem in other papers uses , so it is solved here with . Results for 3000 Ω are given at the end. The reflection and refraction coefficients are the same in both cases.
Data: kV, kV (arrester protective level), .
When the wave reaches the arrester (line end), the Thevenin equivalent is behind , and the arrester holds the voltage at .
(i) Current in the line before reaching the arrester
(ii) Current through the arrester
(iii) Arrester resistance
(iv) Reflection and refraction coefficients
Treat the arrester as a termination :
Check: reflected voltage kV, and kV ✓. Reflected current kA, and kA ✓.
| Quantity | (as printed) | |
|---|---|---|
| Line current | 10 kA | 1 kA |
| Arrester current | 14.33 kA | 1.433 kA |
| Arrester resistance | 118.6 Ω | 1186 Ω |
| / | −0.433 / 0.567 | −0.433 / 0.567 |
| / | 0.433 / 1.433 | 0.433 / 1.433 |
Discussion
- The arrester clamps the voltage at 1700 kV instead of letting it double to 6000 kV at the open end. A negative voltage reflection of −1300 kV travels back along the line.
- The arrester current (14.3 kA) is larger than the line current (10 kA), because current reflection at a low-resistance termination is positive.
- The arrester must be rated to carry this current and to absorb the energy.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Arrester current and resistance (Z = 300 Ω) · High Voltage Engineering, chapter 4 · asked 2×
- Arrester current, resistance and rating on 132 kV line · High Voltage Engineering, chapter 4
- Arrester with 1000 kV BIL on 300 Ω line · High Voltage Engineering, chapter 4 · asked 3×
- Arrester with 1000 kV BIL on 350 Ω line · High Voltage Engineering, chapter 4 · asked 3×
- Surge impedance and velocity of 220 kV line · High Voltage Engineering, chapter 3 · asked 2×
- Transformer BIL and arrester resistance for 500 kV line · High Voltage Engineering, chapter 4
- Arrester separation for a 500 kV/μs surge · High Voltage Engineering, chapter 4