- 2074 Magh · 8 marks
Arrester current, resistance and rating on 132 kV line
Short answer
Arrester current = (2×3000–1700)/300 = 14.33 kA; arrester resistance = 1700/14.33 = 118.6 Ω. Voltage reflection coefficient = –0.433, refraction = 0.567; current reflection = 0.433, refraction = 1.433. The optimal discharge current rating is 14.3 kA, so a 20 kA class arrester is needed.
A surge of 3000 kV is travelling along a 132 kV line. The line surge impedance is 300 ohms and the protective level is 1700 kV. Determine (i) current through the arrester (ii) the value of the arrester resistance for this condition (iii) current and voltage reflection and refraction coefficients (iv) Optimal current rating of the arrester.
When the surge reaches the arrester, the arrester sparks over and holds the line voltage at its protective level . It behaves as a resistance shunting the line, and the arrester current follows from the travelling-wave relations.
Data
- Incident surge voltage, kV
- Protective level of arrester, kV
- Line surge impedance,
- The arrester is treated as the end (termination) of the line.
Incident current
(i) Current through the arrester
The voltage at the arrester is , so the reflected voltage is
The reflected current is kA. The arrester current is
(ii) Arrester resistance
(iii) Reflection and refraction coefficients
With termination on a line of :
Check: kV , and kA .
| Coefficient | Voltage | Current |
|---|---|---|
| Reflection | −0.433 | +0.433 |
| Refraction (transmission) | 0.567 | 1.433 |
(iv) Optimal current rating of the arrester
The arrester must discharge at least kA while keeping its residual voltage at 1700 kV. The optimal (minimum) discharge current rating is therefore about 14.3 kA; in practice the next standard nominal discharge current class, 20 kA (IEC 60099-4 classes: 5, 10, 20 kA), is selected.
Answer: kA, , , , , , rating ≈ 14.3 kA (choose the 20 kA class).
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Arrester current and resistance for 750 kV line · High Voltage Engineering, chapter 4 · asked 2×
- Arrester current and resistance (Z = 300 Ω) · High Voltage Engineering, chapter 4 · asked 2×
- Arrester with 1000 kV BIL on 300 Ω line · High Voltage Engineering, chapter 4 · asked 3×
- Arrester with 1600 kV BIL on 300 Ω line · High Voltage Engineering, chapter 4 · asked 3×
- Transformer BIL and arrester resistance for 500 kV line · High Voltage Engineering, chapter 4
- Arrester with 1000 kV BIL on 350 Ω line · High Voltage Engineering, chapter 4 · asked 3×
- Significance of transmission voltage level, 132 vs 400 kV · Power System Analysis I, chapter 1
- Charging current of 132 kV line, 6 m equilateral · Power System Analysis I, chapter 4
- Charging current of 60 Hz horizontal 132 kV line · Power System Analysis I, chapter 4
- Design: 300 m head plant, GCB rating · Power Plant Design, chapter 4 · asked 11×