- 2070 Bhadra · 6 marks
Charging current of 132 kV line, 6 m equilateral
Short answer
Capacitance per phase is 9.577 nF/km. Charging current per phase is 0.229 A/km.
Determine the charging capacitance and charging current per phase in a 50 Hz, 132 kV, 3-phase overhead line spaced at 6 m from each other and using 18 mm radius conductors per phase.
For equilateral spacing, the capacitance per phase to neutral is .
Data: m, mm m, 132 kV, 50 Hz.
Capacitance per phase
Charging current per phase
(The charging reactive power for all 3 phases is kVAR/km.)
Answer: nF/km (0.00958 µF/km) per phase; A/km per phase.
✓ Answer checked by Claude Opus 5.5 (high effort)