- 2072 Asoj · 8 marks
132 kV triangular line: L, C, charging MVAR
Short answer
With equivalent spacing 4.4814 m, per km: inductance per phase 1.292 mH/km, capacitance 8.958 nF/km, charging current 0.2145 A/km, total three-phase charging reactive power 0.0490 MVAR/km.
A 132 kV, 50 Hz, 3-phase line has its conductors, each of diameter 18 mm, in a triangular configuration. The conductors are transposed at regular intervals. The distances between phase conductors are 4.0 m, 5.0 m and 4.5 m. Find the inductance, capacitance, charging current and charging MVAR per km.
For a transposed line with unsymmetrical spacing, use the equivalent spacing .
Data: diameter 18 mm, m, m; spacings 4.0, 5.0, 4.5 m; 132 kV, 50 Hz.
Inductance per phase
Capacitance per phase
Charging current per km
Charging MVAR per km (three phase)
Answer: mH/km, nF/km, A/km, MVAR/km (49.0 kVAR/km).
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Charging current of 60 Hz horizontal 132 kV line · Power System Analysis I, chapter 4
- Charging current of 132 kV line, 6 m equilateral · Power System Analysis I, chapter 4
- 330 kV quad-bundle line: inductance and charging · Power System Analysis I, chapter 4
- 132 kV horizontal line: susceptance and charging · Power System Analysis I, chapter 4
- ACSR 132 kV line: parameters and charging MVA · Power System Analysis I, chapter 4
- Inductance and capacitance of 4-conductor bundle line · Power System Analysis I, chapter 4
- Inductance of 420 kV line, transposed and untransposed · High Voltage Engineering, chapter 5
- Conductor selection, 100 MW 70 km 132 kV · Transmission and Distribution System Design, chapter 4
- Capacitance matrices, untransposed and transposed (15 m) · High Voltage Engineering, chapter 5 · asked 3×
- Capacitance and charge matrices, transposed and untransposed · High Voltage Engineering, chapter 5