132 kV triangular line: L, C, charging MVAR

Short answer

With equivalent spacing 4.4814 m, per km: inductance per phase 1.292 mH/km, capacitance 8.958 nF/km, charging current 0.2145 A/km, total three-phase charging reactive power 0.0490 MVAR/km.

A 132 kV, 50 Hz, 3-phase line has its conductors, each of diameter 18 mm, in a triangular configuration. The conductors are transposed at regular intervals. The distances between phase conductors are 4.0 m, 5.0 m and 4.5 m. Find the inductance, capacitance, charging current and charging MVAR per km.

For a transposed line with unsymmetrical spacing, use the equivalent spacing Deq=DabDbcDca3D_{eq} = \sqrt[3]{D_{ab}D_{bc}D_{ca}}.

Data: diameter 18 mm, r=0.009r = 0.009 m, r′=0.7788×0.009=0.0070092r' = 0.7788 \times 0.009 = 0.0070092 m; spacings 4.0, 5.0, 4.5 m; 132 kV, 50 Hz.

Deq=4×5×4.53=903=4.4814 mD_{eq} = \sqrt[3]{4 \times 5 \times 4.5} = \sqrt[3]{90} = 4.4814\ \text{m}

Inductance per phase

L=2×10−7ln⁡Deqr′=2×10−7ln⁡4.48140.0070092=2×10−7×6.4605=1.2921×10−6 H/m=1.292 mH/km\begin{aligned} L &= 2\times10^{-7}\ln\frac{D_{eq}}{r'} = 2\times10^{-7}\ln\frac{4.4814}{0.0070092} \\ &= 2\times10^{-7}\times6.4605 = 1.2921\times10^{-6}\ \text{H/m} = 1.292\ \text{mH/km} \end{aligned}

Capacitance per phase

C=2πε0ln⁡(Deq/r)=55.63×10−12ln⁡(4.4814/0.009)=55.63×10−126.2105=8.958×10−12 F/m=8.958 nF/km\begin{aligned} C &= \frac{2\pi\varepsilon_0}{\ln(D_{eq}/r)} = \frac{55.63\times10^{-12}}{\ln(4.4814/0.009)} = \frac{55.63\times10^{-12}}{6.2105} \\ &= 8.958\times10^{-12}\ \text{F/m} = 8.958\ \text{nF/km} \end{aligned}

Charging current per km

XC=12π×50×8.958×10−9=3.553×105 Ω-kmVp=132/3=76.21 kVIc=76 210355 349=0.2145 A/km\begin{aligned} X_C &= \frac{1}{2\pi \times 50 \times 8.958\times10^{-9}} = 3.553\times10^5\ \Omega\text{-km} \\ V_p &= 132/\sqrt3 = 76.21\ \text{kV} \\ I_c &= \frac{76\,210}{355\,349} = 0.2145\ \text{A/km} \end{aligned}

Charging MVAR per km (three phase)

Qc=VL2XC=(132×103)2355 349=49 033 VAR=0.0490 MVAR/kmQ_c = \frac{V_L^2}{X_C} = \frac{(132\times10^3)^2}{355\,349} = 49\,033\ \text{VAR} = 0.0490\ \text{MVAR/km}

Answer: L=1.292L = 1.292 mH/km, C=8.958C = 8.958 nF/km, Ic=0.2145I_c = 0.2145 A/km, Qc=0.0490Q_c = 0.0490 MVAR/km (49.0 kVAR/km).