Short answer

Resistance R = ρl/A = 0.1153 Ω/km. Inductance L = 2×10⁻⁷ ln(D/r') = 1.249 mH/km (XL = 0.3925 Ω/km). Capacitance C = 2πε₀/ln(D/r) = 0.00928 μF/km. Charging current Ic = Vph/Xc = 0.222 A/km, and three-phase charging MVA = √3 VLL Ic = 0.0508 MVAR/km.

A 3-phase 132 kV, 50 Hz line has ACSR conductors of equivalent copper area 1.5 cm² and effective diameter 39.8 mm, spaced equilaterally 8 m apart. (i) Find the line parameters (ii) find the charging current and charging MVA. Resistivity of copper is 1.73×10⁻⁶ Ω-cm.

The line length is not given, so all results are per km. The ACSR conductor is treated as a solid round conductor of the given effective diameter, with GMR r′=0.7788rr' = 0.7788r (no strand data is given).

Data

  • VLL=132V_{LL} = 132 kV, so Vph=132/3=76.21V_{ph} = 132/\sqrt3 = 76.21 kV; f = 50 Hz, ω=314.16\omega = 314.16 rad/s
  • r=39.8/2=19.9r = 39.8/2 = 19.9 mm =1.99= 1.99 cm; D = 8 m = 800 cm (equilateral)
  • Copper-equivalent area A=1.5A = 1.5 cm²; ρ=1.73×10−6 Ω\rho = 1.73\times10^{-6}\ \Omega-cm

(i) Line parameters

Resistance (l = 1 km = 10510^5 cm):

R=ρlA=1.73×10−6×1051.5=0.1153 Ω/kmR = \frac{\rho l}{A} = \frac{1.73\times10^{-6}\times10^5}{1.5} = 0.1153\ \Omega/\text{km}

Inductance: r′=0.7788×1.99=1.5498r' = 0.7788\times1.99 = 1.5498 cm.

L=2×10−7ln⁡Dr′=2×10−7ln⁡8001.5498=2×10−7×6.2465=1.2493 mH/kmXL=314.16×1.2493×10−3=0.3925 Ω/km\begin{aligned} L &= 2\times10^{-7}\ln\frac{D}{r'} = 2\times10^{-7}\ln\frac{800}{1.5498}\\ &= 2\times10^{-7}\times6.2465 = 1.2493\ \text{mH/km}\\ X_L &= 314.16\times1.2493\times10^{-3} = 0.3925\ \Omega/\text{km} \end{aligned}

Capacitance to neutral:

C=2πε0ln⁡(D/r)=5.563×10−11ln⁡(800/1.99)=5.563×10−115.9965=9.277×10−12 F/m=9.277×10−3 μF/kmXC=1ωC=1314.16×9.277×10−9=3.431×105 Ω⋅km\begin{aligned} C &= \frac{2\pi\varepsilon_0}{\ln(D/r)} = \frac{5.563\times10^{-11}}{\ln(800/1.99)} = \frac{5.563\times10^{-11}}{5.9965}\\ &= 9.277\times10^{-12}\ \text{F/m} = 9.277\times10^{-3}\ \mu\text{F/km}\\ X_C &= \frac{1}{\omega C} = \frac{1}{314.16\times9.277\times10^{-9}} = 3.431\times10^5\ \Omega\cdot\text{km} \end{aligned}

(ii) Charging current and charging MVA

Ic=VphXC=76210×314.16×9.277×10−9=0.2221 A/kmQc=3VphIc=3×132×103×0.2221=50.78 kVAR/km=0.0508 MVAR/km\begin{aligned} I_c &= \frac{V_{ph}}{X_C} = 76210\times314.16\times9.277\times10^{-9} = 0.2221\ \text{A/km}\\ Q_c &= 3V_{ph}I_c = \sqrt3\times132\times10^3\times0.2221\\ &= 50.78\ \text{kVAR/km} = 0.0508\ \text{MVAR/km} \end{aligned}
ParameterValue per phase per km
R0.1153 Ω
L (XLX_L)1.249 mH (0.3925 Ω)
C (XCX_C)0.009277 μF (343.1 kΩ·km)
Charging current0.2221 A
Charging MVA (3-phase)0.0508 MVAR

Answer: R = 0.115 Ω/km, L = 1.249 mH/km, C = 0.00928 μF/km; charging current 0.222 A/km and charging MVA 0.0508 MVAR/km. For example, a 100 km line would draw 22.2 A and 5.08 MVAR.