- 2081 Chaitra (new course) · 3+3 marks
ACSR 132 kV line: parameters and charging MVA
Short answer
Resistance R = ρl/A = 0.1153 Ω/km. Inductance L = 2×10⁻⁷ ln(D/r') = 1.249 mH/km (XL = 0.3925 Ω/km). Capacitance C = 2πε₀/ln(D/r) = 0.00928 μF/km. Charging current Ic = Vph/Xc = 0.222 A/km, and three-phase charging MVA = √3 VLL Ic = 0.0508 MVAR/km.
A 3-phase 132 kV, 50 Hz line has ACSR conductors of equivalent copper area 1.5 cm² and effective diameter 39.8 mm, spaced equilaterally 8 m apart. (i) Find the line parameters (ii) find the charging current and charging MVA. Resistivity of copper is 1.73×10⁻⁶ Ω-cm.
The line length is not given, so all results are per km. The ACSR conductor is treated as a solid round conductor of the given effective diameter, with GMR (no strand data is given).
Data
- kV, so kV; f = 50 Hz, rad/s
- mm cm; D = 8 m = 800 cm (equilateral)
- Copper-equivalent area cm²; -cm
(i) Line parameters
Resistance (l = 1 km = cm):
Inductance: cm.
Capacitance to neutral:
(ii) Charging current and charging MVA
| Parameter | Value per phase per km |
|---|---|
| R | 0.1153 Ω |
| L () | 1.249 mH (0.3925 Ω) |
| C () | 0.009277 μF (343.1 kΩ·km) |
| Charging current | 0.2221 A |
| Charging MVA (3-phase) | 0.0508 MVAR |
Answer: R = 0.115 Ω/km, L = 1.249 mH/km, C = 0.00928 μF/km; charging current 0.222 A/km and charging MVA 0.0508 MVAR/km. For example, a 100 km line would draw 22.2 A and 5.08 MVAR.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Charging current of 60 Hz horizontal 132 kV line · Power System Analysis I, chapter 4
- Charging current of 132 kV line, 6 m equilateral · Power System Analysis I, chapter 4
- 132 kV triangular line: L, C, charging MVAR · Power System Analysis I, chapter 4
- Charging VAR of 132 kV equilateral line · Power System Analysis I, chapter 4
- Nominal-T 100 km line, 50 MVA at 132 kV · Power System Analysis I, chapter 6
- 132 kV horizontal line: susceptance and charging · Power System Analysis I, chapter 4
- 50 kVA transformer: equivalent parameters, copper loss · Electrical Machines, chapter 2
- Conductor selection, 100 MW 70 km 132 kV · Transmission and Distribution System Design, chapter 4
- Equivalent impedance and copper loss of 50 kVA transformer · Electrical Machines I, chapter 2
- Air clearances for 132 kV double circuit line · Transmission and Distribution System Design, chapter 4