- 2074 Bhadra · 8 marks
Air clearances for 132 kV double circuit line
Short answer
Air clearance is 1.6 m (based on 145 kV peak/rms criteria). Insulator string length is 1.4 m (7 discs). Cross-arm length is 2.6 m (clearance plus swing). Vertical spacing is 3.0 m, horizontal spacing is 6.4 m. Earth wire height above top conductor is 5.6 m for a 30° shielding angle.
For a double circuit, 132 kV transmission line, find the following air clearance with justifications. i) Cross arm length ii) Insulator string length iii) Horizontal and vertical separation of conductor iv) Height of earth wire from top most conductor.
[Given in appendix: Minimum air clearance: I. 1 cm for 1 kV (maximum per phase peak) and factor of safety is 30 cm; II. 6.5 inch per 10 kV (maximum per phase rms) and factor of safety is 8 inch.]
The dimensions follow from the minimum phase-to-earth air clearance, the insulator string length and the insulator swing.
Assumptions: maximum system voltage 145 kV; swing 45°; disc 254 × 154 mm; tower width at cross-arm level 1.2 m.
Minimum air clearance
Take the larger value: a ≈ 1.6 m.
ii) Insulator string length
For 145 kV, Table A-3 gives:
- wet withstand 230 kV needs 6 discs (250 kV),
- impulse 550 kV needs 6 discs (610 kV),
- dry withstand 265 kV needs 4 discs.
Adding one spare disc gives 7 discs:
Common practice uses 9 discs (about 1.6 m) where pollution is a concern.
i) Cross-arm length
This keeps clearance from the tower body when the string swings by 45°.
iii) Separation of conductors
- Vertical (between cross-arms on the same side):
The hanging conductor keeps clearance from the cross-arm below.
- Horizontal (between the two circuits across the tower):
This is well above the phase-to-phase clearance of about m.
ew (earth wire)
|
o---------+---------o top \
| | 3.0 m
o---------+---------o middle /
|
o---------+---------o bottom
|<-2.6->|1.2|<-2.6->|
iv) Height of earth wire above the top conductor
One earth wire at the peak is enough for a 132 kV double-circuit vertical tower. For a 30° shielding angle, the horizontal distance to the outer conductor is m:
| Item | Value |
|---|---|
| Air clearance | 1.6 m |
| Cross-arm length | 2.6 m |
| String length | 1.4 m (7 discs) |
| Vertical / horizontal spacing | 3.0 m / 6.4 m |
| Earth wire above top conductor | 5.6 m |
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Air clearances for 220 kV double circuit line · Transmission and Distribution System Design, chapter 4
- Air clearances, 220 kV line for 200 MW · Transmission and Distribution System Design, chapter 4
- Tower dimensions for 220 kV double circuit line · Transmission and Distribution System Design, chapter 4 · asked 2×
- Initial line design for 200 MW over 120 km · Transmission and Distribution System Design, chapter 2
- Tower dimensions for 220 kV single circuit line · Transmission and Distribution System Design, chapter 4 · asked 2×
- Air clearances for 220 kV single circuit line · Transmission and Distribution System Design, chapter 4
- True/false: cross-arm length and string efficiency · High Voltage Engineering, chapter 5
- 132 kV horizontal line: susceptance and charging · Power System Analysis I, chapter 4
- Charging current of 60 Hz horizontal 132 kV line · Power System Analysis I, chapter 4
- Inductive reactance of vertical 132 kV line · Power System Analysis I, chapter 4
All Transmission and Distribution System Design chapter 4 questions →