- 2073 Bhadra · 8 marks
Air clearances for 220 kV single circuit line
Short answer
For 245 kV max voltage, phase-to-earth clearance is 2.54 m, phase-to-phase 2.9 m. With 11-disc insulator string length 2.0 m and swing angle 45°, cross-arm length is 4.0 m. Vertical span spacing is 4.5 m, horizontal 9.5 m, earth wire above top conductor 8.3 m, and ground clearance 6.91 m.
Compute the various air clearances required for a 220 kV single circuit transmission line.
The air clearances of a 220 kV single-circuit line are found from the maximum system voltage, the insulator string and its swing. Assumptions: kV, swing 45°, 254 × 154 mm discs, tower width at cross-arm level 1.5 m.
1. Phase-to-earth (tower) clearance
Adopt the larger value, a = 2.54 m.
2. Phase-to-phase clearance
The actual spacing chosen below is much larger.
3. Insulator string length
10 discs meet the wet (395 kV) and impulse (900 kV) levels. Adding one spare gives 11 discs:
4. Cross-arm length (clearance with swing)
5. Vertical spacing between conductors
6. Horizontal spacing between conductors on opposite sides
7. Earth wire clearance (shielding angle 30°, one earth wire)
Also check the midspan clearance between the earth wire and the conductor, using the IS 5613 rule of thumb: at least m, about 4.6 m for a 300 m span.
8. Minimum ground clearance
This compares with 7.0 m in IS practice.
| Clearance | Value |
|---|---|
| Phase to earth | 2.54 m |
| Phase to phase (minimum) | 2.9 m |
| Cross-arm length | 4.0 m |
| Vertical / horizontal conductor spacing | 4.5 m / 9.5 m |
| Earth wire above top conductor | 8.3 m |
| Ground clearance | 6.91 m |
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Air clearances for 220 kV double circuit line · Transmission and Distribution System Design, chapter 4
- Air clearances, 220 kV line for 200 MW · Transmission and Distribution System Design, chapter 4
- Air clearances for 132 kV double circuit line · Transmission and Distribution System Design, chapter 4
- Tower dimensions for 220 kV single circuit line · Transmission and Distribution System Design, chapter 4 · asked 2×
- Number of insulator discs for 220 kV line · Transmission and Distribution System Design, chapter 3
- Tower dimensions for 220 kV double circuit line · Transmission and Distribution System Design, chapter 4 · asked 2×
- Capacitor for zero regulation, 70 km 220 kV line · Power System Analysis I, chapter 6
- RRRV from short circuit test (220 kV) · Switchgear and Protection, chapter 6 · asked 2×
- Surge impedance and velocity of 220 kV line · High Voltage Engineering, chapter 3 · asked 2×
- 220 kV line, 200 MW: sending end from ABCD · Power System Analysis I, chapter 6
All Transmission and Distribution System Design chapter 4 questions →