Skip to main content

RRRV from short circuit test (220 kV)

Short answer

For the grounded fault, V_r=144.37 kV and peak restriking voltage is 288.75 kV reached at 27.78 μs, so average RRRV is 10.39 kV/μs; maximum instantaneous RRRV is 16.33 kV/μs.

In a short circuit test on a 220 kV 3-phase system, the breaker gave the following results: p.f. of the fault 0.45, recovery voltage 0.9 of full line value; the breaking current is symmetrical and the restriking transient had a natural frequency of 18 kHz. Determine the rate of rise of restriking voltage. Assume that the fault is grounded.

The RRRV is the rate at which the voltage across the CB contacts rises after the arc is extinguished at current zero.

Method

  • Peak phase voltage: V_m = √2 × V_L/√3.
  • At current zero the instantaneous system voltage is V_m sin φ (fault current lags by φ, cos φ = fault p.f.).
  • Active recovery voltage: V_r = k × sin φ × V_m, where k is the recovery voltage factor (0.9 of full line value).
  • For an ungrounded symmetrical fault the first pole to clear would see 1.5 times this (first-pole-to-clear factor 1.5); here the fault is grounded, so the factor is 1.
  • Restriking voltage peak = 2 V_r, reached at t = 1/(2f_n).
  • RRRV (average up to the peak, the usual textbook value) = 2V_r / t = 4 f_n V_r. The maximum instantaneous rate is ω_n V_r.

Data

V_L = 220 kV, cos φ = 0.45, k = 0.9, f_n = 18 kHz, fault grounded (factor 1).

sin φ = √(1 − 0.45²)          = 0.8930
V_m   = √2 × 220/√3           = 179.63 kV
V_r   = 0.9 × 0.8930 × 179.63 = 144.37 kV
Peak restriking = 2 V_r       = 288.75 kV
t = 1/(2 f_n) = 1/(2×18000)   = 27.78 μs
RRRV = 288.75 kV / 27.78 μs   = 10.39 kV/μs

Maximum instantaneous rate (at t = 1/(4f_n) = 13.9 μs):

ω_n V_r = 2π × 18000 × 144.37 kV
        = 16.33 kV/μs

Answer: RRRV ≈ 10.39 kV/μs (average up to the first peak of 288.75 kV); maximum instantaneous RRRV ≈ 16.33 kV/μs.

✓ Answer checked by Claude Opus 5.5 (high effort)

All Switchgear and Protection chapter 6 questions →