- 2078 Chaitra · 4 marks
Breaking MVA and making kA (800 A, 33 kV)
Short answer
Breaking capacity = √3 × 33 kV × 25 kA = 1429 MVA. Making capacity = 2.55 × 25 = 63.75 kA peak.
Calculate breaking capacity in MVA and making capacity in kA of a 3 phase circuit breaker with following parameters: Rated current = 800 A; Rated voltage = 33 kV; Ibsym = 25 kA.
Breaking capacity is the MVA corresponding to the symmetrical breaking current at rated voltage, and making capacity is the peak current the CB can close onto, taken as 2.55 times the symmetrical breaking current.
Given
Rated current = 800 A (normal current, not used for these values), V = 33 kV, I_b(sym) = 25 kA.
Breaking capacity
Breaking MVA = √3 × V × I_b
= √3 × 33 kV × 25 kA
= 1428.9 MVA
Making capacity
I_making = 1.8 × √2 × I_b = 2.55 × I_b
= 2.55 × 25
= 63.75 kA (peak)
Answer: Breaking capacity ≈ 1429 MVA; making capacity = 63.75 kA (peak).
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Breaking, making, short-time ratings (500 MVA) · Switchgear and Protection, chapter 6
- CB ratings: 2500 A, 1500 MVA, 33 kV · Switchgear and Protection, chapter 6
- CB ratings: 33 kV, 1500 A, 3000 MVA · Switchgear and Protection, chapter 6
- CB terms: making, breaking, operating duty · Switchgear and Protection, chapter 6
- Specifying breaker on 132/66 kV transformer · Switchgear and Protection, chapter 6
- Selecting CB for 6.6 kV, 650 MVA · Switchgear and Protection, chapter 6
- Short circuit MVA of feeder circuit breaker · Power System Analysis II, chapter 3 · asked 2×
- Compensation capacity for 15 MW, 33 kV load · Power System Analysis I, chapter 6
- Current chopping overvoltage in 132 kV breaker · High Voltage Engineering, chapter 3
- ACSR 132 kV line: parameters and charging MVA · Power System Analysis I, chapter 4