- 2075 Baisakh · 4 marks
CB terms: making, breaking, operating duty
Short answer
Making capacity is the peak closing current including DC offset, equal to 2.55 times the symmetrical breaking current. Breaking capacity is the rms symmetrical current or √3×V×I in MVA. Operating duty is the specified O–t–CO–t′–CO sequence; rated current is the continuous rms current without exceeding temperature limits.
Explain the terms related to Circuit Breaker: i) Making Capacity ii) Breaking Capacity iii) Operation Duty iv) Rated Current.
These terms define the ratings of a circuit breaker as per IEC 62271-100 / IS 13118.
i) Making capacity
The peak value of current that the CB can make (close on to) at rated voltage when closing on a short circuit, including the DC offset of the first cycle. The contacts must withstand the large electromagnetic force at this first peak.
Making current = 1.8 × √2 × I_b = 2.55 × I_b (peak)
ii) Breaking capacity
The largest current the CB can break at rated voltage under specified conditions. Expressed as the rms symmetrical breaking current I_b (kA) or as MVA:
Breaking capacity (MVA) = √3 × V(kV) × I_b(kA)
Asymmetrical breaking current includes the DC component at contact separation.
iii) Operating duty
The sequence of operations the CB must perform at rated breaking current, with given time intervals. Standard duties:
- O – t – CO – t′ – CO, e.g. O – 3 min – CO – 3 min – CO (non-auto-reclose duty)
- O – 0.3 s – CO – 3 min – CO (rapid auto-reclosing duty)
Here O = open, CO = close followed immediately by open, t = dead time. The CB must keep its rated breaking capacity throughout this sequence.
iv) Rated current
The rms value of normal current the CB can carry continuously at rated frequency without the temperature of any part exceeding its permitted limit. Standard values: 400, 630, 800, 1250, 1600, 2000, 2500, 3150 A, etc.
Example: a 33 kV CB rated 1250 A, 25 kA, duty O–0.3 s–CO–3 min–CO has breaking capacity √3 × 33 × 25 = 1429 MVA and making capacity 2.55 × 25 = 63.75 kA peak.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Breaking, making, short-time ratings (500 MVA) · Switchgear and Protection, chapter 6
- Breaking MVA and making kA (800 A, 33 kV) · Switchgear and Protection, chapter 6
- HVDC circuit breaker operation · Switchgear and Protection, chapter 6
- CB ratings: 2500 A, 1500 MVA, 33 kV · Switchgear and Protection, chapter 6
- CB ratings: 33 kV, 1500 A, 3000 MVA · Switchgear and Protection, chapter 6
- Specifying breaker on 132/66 kV transformer · Switchgear and Protection, chapter 6
- Short circuit MVA of feeder circuit breaker · Power System Analysis II, chapter 3 · asked 2×
- Boundary layer concept and related terms · Fluid Mechanics, chapter 8
- Reactor to protect circuit breaker of small station · Power Plant Equipment, chapter 4
- Soil moisture tension and related terms · Irrigation and Drainage Engineering, chapter 2