- 2070 Magh · 8 marks
Specifying breaker on 132/66 kV transformer
Short answer
Rated continuous current is 437.4 A (standard 630 A) calculated as 50 MVA/(√3×66 kV). Breaking capacity is 357.14 MVA (3.12 kA) from fault MVA = 50 MVA/0.14.
Figure shows a 132/66 kV power transformer is fed from an infinite bus. If the 66 kV bus is a load bus, specify for the breaker 'X': i) Rated continuous current ii) Breaking capacity in MVA. [Figure: Infinite bus – breaker Y – 3-phase 132/66 kV, 50 MVA transformer with Z = 14% – breaker X – load bus.]
Breaker X is on the 66 kV side, between the transformer and the load bus. It must carry the full-load current of the transformer continuously, and it must interrupt the fault current that flows through it for a fault just beyond it (on the load bus).
Assumptions: the source is an infinite bus (zero impedance), the load bus has no other source, and the fault current is limited only by the transformer impedance (14% on a 50 MVA base).
i) Rated continuous current
I_rated = S / (√3 × V)
= 50 × 10⁶ / (√3 × 66 × 10³)
= 437.39 A
So breaker X must have a continuous current rating of at least 437.4 A; the next standard rating, 630 A, is chosen (IEC R10 series).
ii) Breaking capacity
For a three-phase fault on the load bus (just after X), the only impedance is the transformer reactance:
Fault MVA = Base MVA / Z(pu)
= 50 / 0.14
= 357.14 MVA
Fault current at 66 kV:
I_f = 357.14 × 10⁶ / (√3 × 66 × 10³)
= 3124.2 A ≈ 3.12 kA
A fault on the transformer side of X is fed directly from the infinite bus and is cleared by breaker Y, so X only has to break the current fed through the transformer.
Making current (peak, first cycle) = 2.55 × 3.124 = 7.97 kA.
Answer: rated continuous current = 437.4 A (choose the 630 A standard); breaking capacity = 357.14 MVA (about 3.12 kA at 66 kV). In practice a standard 72.5 kV, 630 A breaker with a rated short-circuit breaking current of 12.5 kA (the lowest standard value commonly offered at this voltage, well above the required 3.12 kA) would be specified.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Breaking MVA and making kA (800 A, 33 kV) · Switchgear and Protection, chapter 6
- Breaking, making, short-time ratings (500 MVA) · Switchgear and Protection, chapter 6
- IDMT relays across 132/33 kV transformer (2700 A) · Switchgear and Protection, chapter 7
- IDMT relays across 132/33 kV transformer (2000 A) · Switchgear and Protection, chapter 7
- IDMT relays across 132/11 kV transformer (3500 A) · Switchgear and Protection, chapter 7
- CB ratings: 2500 A, 1500 MVA, 33 kV · Switchgear and Protection, chapter 6
- Current chopping overvoltage in 132 kV breaker · High Voltage Engineering, chapter 3
- Nominal-T 100 km line, 50 MVA at 132 kV · Power System Analysis I, chapter 6
- Design: 500 kVA 66/11 kV power transformer · Electric Machine Design, chapter 3 · asked 6×
- Design: 4000 kVA 66/11 kV power transformer · Electric Machine Design, chapter 3 · asked 5×