- 2073 Bhadra · 3+5 marks
Breaking, making, short-time ratings (500 MVA)
Short answer
Rated symmetrical breaking current is the rms AC component the CB can interrupt; making capacity is the peak withstand (2.55×I_b); short time rating is the rms carry current for specified time. For 500 MVA, 11 kV: I_b = 26.24 kA rms, making = 66.92 kA peak, short time = 26.24 kA for 3 s.
Explain what do you understand by: i) Rated symmetrical breaking current ii) Making capacity iii) Short time current rating. Obtain their value for a three phase CB rated as 500 A, 500 MVA, 11 kV, 3 sec.
i) Rated symmetrical breaking current
The rms value of the AC (symmetrical) component of the short-circuit current that the CB can interrupt at its rated voltage, at the instant of contact separation. It is the basis of the breaking capacity:
Breaking capacity (MVA) = √3 × V(kV) × I_b(kA)
ii) Making capacity
The peak value of current (including the DC offset) during the first cycle that the CB can safely make when it closes on a short circuit. The contacts must withstand the large electromagnetic forces at the first major peak, which can be 1.8 times the symmetrical peak:
I_making = 1.8 × √2 × I_b = 2.55 × I_b (peak)
iii) Short time current rating
The rms current the CB can carry in the closed position for a stated short time (1 s or 3 s) without thermal or mechanical damage, while a downstream breaker clears the fault. It is usually equal to the rated symmetrical breaking current for the given time.
Calculation for 500 A, 500 MVA, 11 kV, 3 s CB
I_b = 500 / (√3 × 11)
= 26.24 kA (rms)
I_making = 2.55 × 26.24
= 66.92 kA (peak)
Short time rating = 26.24 kA (rms) for 3 s
Answer: Rated symmetrical breaking current = 26.24 kA rms; making capacity = 66.92 kA peak; short time rating = 26.24 kA for 3 s. (Rated normal current = 500 A, rated voltage = 11 kV.)
Note that the 33 kV, 1500 MVA breaker and this 11 kV, 500 MVA breaker have the same breaking current, because MVA and voltage are in the same ratio.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- CB ratings: 2500 A, 1500 MVA, 33 kV · Switchgear and Protection, chapter 6
- CB ratings: 33 kV, 1500 A, 3000 MVA · Switchgear and Protection, chapter 6
- Breaking MVA and making kA (800 A, 33 kV) · Switchgear and Protection, chapter 6
- CB terms: making, breaking, operating duty · Switchgear and Protection, chapter 6
- Selecting CB for 6.6 kV, 650 MVA · Switchgear and Protection, chapter 6
- Differential protection: 11 kV, 100 MVA generator · Switchgear and Protection, chapter 7
- Design: 500 kVA 66/11 kV power transformer · Electric Machine Design, chapter 3 · asked 6×
- Initial symmetrical current, load short circuit · Power System Analysis II, chapter 3
- Reactance diagram: 50 MVA, 13.8 kV base, three generators · Power System Analysis I, chapter 3
- Arrester current, resistance and rating on 132 kV line · High Voltage Engineering, chapter 4