- 2071 Magh · 8 marks
Selecting CB for 6.6 kV, 650 MVA
Short answer
Rated current is 175 A (standard 630 A), breaking current 56.9 kA, making current 145 kA. Specify a 7.2 kV, 630 A, 63 kA vacuum circuit breaker.
Select a circuit breaker for the following application: 6.6 kV, 650 MVA (breaking capacity) breaker. It is supposed to be connected to primary of 6600/433 V, 2000 kVA transformer. Justify your choice and prepare the specifications for the breaker.
The breaker controls the 6.6 kV primary of a 2000 kVA, 6600/433 V distribution transformer and must interrupt 650 MVA at 6.6 kV.
Calculations
Rated (normal) current:
I_n = 2000 × 10³ / (√3 × 6600) = 174.95 A
Symmetrical breaking current:
I_b = 650 × 10⁶ / (√3 × 6600) = 56 860 A ≈ 56.86 kA
Making current (peak):
I_m = 2.55 × I_b = 2.55 × 56.86 = 144.99 kA ≈ 145 kA
Short-time current (1 s or 3 s) = I_b ≈ 56.86 kA
Choice of breaker and justification
A vacuum circuit breaker (indoor, withdrawable type) is chosen:
- 6.6 kV is in the medium voltage range, where vacuum breakers are standard and have the lowest lifetime cost.
- Vacuum gives fast recovery of dielectric strength, very low contact erosion and long life (10,000+ operations) with almost no maintenance.
- No fire hazard (no oil) and no gas handling (unlike SF6), so it suits indoor switchgear near the transformer.
- Compact size; suitable for transformer switching. An SF6 breaker of the same rating is an acceptable alternative; older practice would have used a minimum oil breaker.
- Transformer magnetising current is small; modern vacuum interrupters have a low chopping current, and surge arresters at the transformer terminals take care of switching surges.
Specification of the breaker (as per IEC 62271-100 standard values)
| Parameter | Value |
|---|---|
| Type | Indoor, 3-pole vacuum CB, withdrawable |
| Rated voltage | 7.2 kV (system 6.6 kV) |
| Rated frequency | 50 Hz |
| Rated normal current | 630 A (required 175 A) |
| Rated short-circuit breaking current | 63 kA symmetrical (required 56.86 kA) |
| Rated breaking capacity | ≥ 650 MVA at 6.6 kV |
| Rated making current | 157.5 kA peak (2.5 × 63 kA; required 145 kA) |
| Rated short-time withstand current | 63 kA for 3 s |
| Rated operating sequence | O – 0.3 s – CO – 3 min – CO |
| Power frequency withstand | 20 kV rms for 1 min |
| Lightning impulse withstand | 60 kV peak |
| Opening / break time | about 3 cycles (60 ms) |
| Operating mechanism | Motor-wound spring, 110 V DC trip and close coils |
| Protection | IDMT overcurrent + earth fault relay through CTs 200/5 A |
Answer: rated current 174.95 A (630 A standard), breaking current 56.86 kA, making current 145 kA; a 7.2 kV, 630 A, 63 kA vacuum circuit breaker is specified.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Breaking MVA and making kA (800 A, 33 kV) · Switchgear and Protection, chapter 6
- Specifying breaker on 132/66 kV transformer · Switchgear and Protection, chapter 6
- CB ratings: 2500 A, 1500 MVA, 33 kV · Switchgear and Protection, chapter 6
- CB ratings: 33 kV, 1500 A, 3000 MVA · Switchgear and Protection, chapter 6
- Breaking, making, short-time ratings (500 MVA) · Switchgear and Protection, chapter 6
- CB terms: making, breaking, operating duty · Switchgear and Protection, chapter 6
- Design: 25 kVA 11000/433 V distribution transformer · Electric Machine Design, chapter 3
- Short circuit MVA of feeder circuit breaker · Power System Analysis II, chapter 3 · asked 2×
- Design: 100 kVA 4000/433 V distribution transformer · Electric Machine Design, chapter 3 · asked 4×
- Design: 150 kVA 6600/400 V distribution transformer · Electric Machine Design, chapter 3 · asked 5×