- 2077 Chaitra · 4 marks
CB ratings: 33 kV, 1500 A, 3000 MVA
Short answer
Rated symmetrical breaking current = 3000/(√3×33) = 52.49 kA rms. Making current = 2.55×52.49 = 133.8 kA peak. Short time rating = 52.49 kA for 1 s.
Determine the rated symmetrical breaking current, making current and short time rating of a circuit breaker with following parameters: 33 kV, 1500 A, 3000 MVA, 1 sec.
The breaking, making and short-time currents of a CB are fixed by its rated MVA and voltage.
Definitions and formulas used
- Rated symmetrical breaking current I_b = rated breaking MVA / (√3 × rated line kV), rms.
- Rated making current = 1.8 × √2 × I_b = 2.55 × I_b (peak), since the first major peak of an asymmetrical current can be 1.8 times the peak of the symmetrical current.
- Short time rating = the current the CB can carry while closed for the stated time without damage; it equals I_b for the given duration.
Given
33 kV, 1500 A, 3000 MVA, 1 s.
I_b = 3000 / (√3 × 33)
= 52.49 kA (rms)
I_making = 2.55 × 52.49
= 133.84 kA (peak)
Short time rating = 52.49 kA (rms) for 1 s
Answer: Rated symmetrical breaking current = 52.49 kA rms; making current = 133.8 kA peak; short time rating = 52.49 kA for 1 s.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- CB ratings: 2500 A, 1500 MVA, 33 kV · Switchgear and Protection, chapter 6
- Breaking, making, short-time ratings (500 MVA) · Switchgear and Protection, chapter 6
- Breaking MVA and making kA (800 A, 33 kV) · Switchgear and Protection, chapter 6
- CB terms: making, breaking, operating duty · Switchgear and Protection, chapter 6
- Selecting CB for 6.6 kV, 650 MVA · Switchgear and Protection, chapter 6
- Short circuit MVA of feeder circuit breaker · Power System Analysis II, chapter 3 · asked 2×