Design: 25 kVA 11000/433 V distribution transformer
Short answer
Core: d=134.5 mm, limb 114.4×71.3 mm; window 114.9×287.3 mm; yoke depth 114.4 mm, height 118.2 mm. Overall frame 523.6×613.2×114.4 mm. Per-unit resistance, reactance, regulation, and efficiency are not fully computed in the provided solution.
Design a 25 kVA, 11000/433 V, 50 Hz, 3 phase, delta/star core type distribution transformer. The required data for design are given below: Maximum flux density in core = 1 Wb/m²; Current density in conductor = 2.3 A/mm²; Constant for output volt per turn, K = 0.45; Core type = cruciform; Window space factor, Kw = 8/(30+kV); Stacking factor = 0.9; Ratio of window height to width = 2.5; Take area of yoke 20% more than area of limb; Width of LV winding = 9.1 mm; Width of HV winding = 26.22 mm; Total losses at full load = 901 W. Calculate: i) Dimensions of core, window and yoke ii) Overall dimensions of the frame iii) Per unit resistance and leakage reactance drop iv) Per unit voltage regulation at 0.8 pf v) Full load efficiency at 0.8 pf
Standard method (A.K. Sawhney, A Course in Electrical Machine Design): , net core area ratio for the core type, output equation for the window, yoke depth = width of largest stamping. Assumed: clearance core-to-LV 2 mm, LV-to-HV duct 15 mm, end clearance 20 mm, -mm²/m.
i) Dimensions of core, window and yoke
Voltage per turn, ( in kVA, total for 3 phases):
For a cruciform (two-stepped) core with stacking factor 0.9, (standard ratio, Sawhney):
Gross core area m².
Output equation (three phase):
Window space factor
Yoke:
Yoke area 20% more than core area (hot-rolled steel, to reduce yoke loss and magnetising current). Yoke depth = width of largest stamping:
ii) Overall dimensions of frame
+-----------------------------+ ---
| top yoke | ^
+-----+-----+-----+-----+-----+ |
|limb | |limb | |limb | |
| R | Ww | Y | Ww | B | H
| | | | | | |
+-----+-----+-----+-----+-----+ |
| bottom yoke | v
+-----------------------------+ ---
|<------------ W ------------>|
|<--- D --->|<--- D --->|
iii) Per unit resistance and leakage reactance drop
Phase voltages: LV (star) V; HV (delta) V.
Phase currents: A; A.
Radial build (assumed clearance between core and LV = 2 mm):
| Item | Inside dia (mm) | Outside dia (mm) |
|---|---|---|
| LV winding | 138.5 | 156.7 |
| HV winding | 186.7 | 239.2 |
Radial depths: mm (LV), mm (HV), duct mm. Axial length mm.
Mean lengths of turn:
Check: HV outside diameter 239 mm vs = 249 mm. Adjacent HV coils have about 10 mm clearance, so the coils fit.
Resistance referred to HV, with (copper at about 75 °C):
Leakage reactance (per unit), with per limb and axial winding length mm:
iv) Per unit regulation at 0.8 pf lagging
v) Full-load efficiency at 0.8 pf
Output kW; total full-load loss = 901 W.
(Copper loss from the resistance above: = 607 W, so the iron loss is about 294 W.)
Answer: = 134.5 mm, window 115 × 287 mm; frame 524 × 613 × 114 mm; = 0.0243, = 0.0417; regulation ≈ 4.44%; efficiency ≈ 95.69%.
✓ Answer checked by Claude Sonnet 5.5
Related questions
- Design: 100 kVA 4000/433 V distribution transformer · Electric Machine Design, chapter 3 · asked 4×
- Design: 150 kVA 11000/440 V transformer with tubes · Electric Machine Design, chapter 3
- Design: 150 kVA 11000/420 V distribution transformer · Electric Machine Design, chapter 3 · asked 3×
- Design: 150 kVA 6600/400 V distribution transformer · Electric Machine Design, chapter 3 · asked 5×
- Design: 25 kVA transformer frame, regulation, tubes · Electric Machine Design, chapter 3 · asked 2×
- Design data: 1000 kVA 66/11 kV transformer · Electric Machine Design, chapter 3
- 500 kVA delta/star transformer efficiency · Electrical Machine, chapter 2
- 25 kVA ideal transformer currents, flux · Basic Electrical and Electronics Engineering, chapter 2
- Delta/star 120 kVA transformer values · Electrical Machine, chapter 2
- 3-phase 500 kVA transformer primary current · Electrical Machines, chapter 2