Current chopping overvoltage in 132 kV breaker
Short answer
The surge impedance of the transformer-bushing circuit is sqrt(L/C) = sqrt(5/10⁻⁸) = 22.36 kΩ. Chopping 10 A gives V = 10 × 22.36 kΩ = 223.6 kV across the breaker poles. The oscillation frequency is 1/(2π√(LC)) ≈ 712 Hz.
In a 132 kV circuit breaker the bushing to ground capacitance is 0.01 μF and the transformer inductance succeeding the circuit breaker is 5 H. Calculate the voltage appearing across the poles of the circuit breaker if it breaks magnetizing current of 10 A flowing in the transformer.
When the breaker chops the magnetising current , the energy in the transformer inductance moves to the bushing capacitance:
Data: H, F. The current is chopped at an instantaneous value of A.
Surge impedance of the transformer–bushing circuit
Voltage across the breaker poles
Frequency of oscillation
For comparison, the normal peak phase voltage of a 132 kV system is kV. The chopping overvoltage is therefore about 2.07 times the normal peak. This voltage appears across the open contacts and can cause restriking.
Answer: voltage across the breaker poles ≈ 223.6 kV (oscillating at about 712 Hz).
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Current chopping overvoltage at zero and peak · High Voltage Engineering, chapter 3
- Overvoltage due to chopping of magnetising current · High Voltage Engineering, chapter 3
- Surge voltage at transformer with capacitance · High Voltage Engineering, chapter 3
- Arrester current, resistance and rating on 132 kV line · High Voltage Engineering, chapter 4
- Specifying breaker on 132/66 kV transformer · Switchgear and Protection, chapter 6
- IDMT relays across 132/33 kV transformer (2000 A) · Switchgear and Protection, chapter 7
- IDMT relays across 132/11 kV transformer (3500 A) · Switchgear and Protection, chapter 7
- IDMT relays across 132/33 kV transformer (2700 A) · Switchgear and Protection, chapter 7