- 2074 Magh · 8 marks
Current chopping overvoltage at zero and peak
Short answer
Peak magnetising current is 7√2 = 9.90 A and normal peak phase voltage is 107.8 kV. Interrupted at zero current, Vm = 107.8 kV with no chopping overvoltage. Interrupted at peak current, Vm = 9.90 × sqrt(5/0.01 μF) ≈ 221.4 kV.
In a 132 kV circuit breaker, the bushing to ground capacitance is 0.01 μF and the transformer impedance succeeding the CB is 5 H. The circuit breaker interrupts the magnetizing current of 7 A (rms). Calculate the possible overvoltage due to current chopping i) When magnetizing current is interrupted at zero value ii) When magnetizing current is interrupted at peak value
Current chopping transfers the energy stored in the transformer inductance to the bushing-to-ground capacitance:
Here is the current and is the capacitor voltage at the instant of interruption.
Data: H, F, A.
Peak magnetising current: A.
Peak system phase voltage: kV.
The magnetising current lags the voltage by about . So when the current is zero the voltage is at its peak, and when the current is at its peak the voltage is zero.
(i) Interrupted at current zero
, so the magnetic energy is .
No energy is released into the capacitance. The only voltage left is the normal system peak (107.8 kV), which decays. Overvoltage due to chopping = 0. This is the ideal case.
(ii) Interrupted at peak current
A and .
This is times the normal peak phase voltage.
| Case | at cut | Voltage (kV) |
|---|---|---|
| Current zero | 0 A | 107.8 (normal peak, no overvoltage) |
| Current peak | 9.90 A | 221.4 |
The oscillation frequency is Hz.
Answer: (i) no chopping overvoltage; the voltage stays at the normal peak of 107.8 kV. (ii) 221.4 kV.
✓ Answer checked by Claude Opus 5.5 (high effort)