Overvoltage due to chopping of magnetising current

Short answer

Chopping forces the magnetising current to zero early, trapping energy ½Li² in the transformer inductance. This energy oscillates with stray capacitance C, giving peak voltage Vm = sqrt(v² + (L/C)i²). Interrupting at natural current zero leaves i=0, so Vm equals normal peak voltage; no overvoltage.

Describe how the switching overvoltage takes place due to chopping of the magnetising current. Also show that the effect is minimum when switching takes place at zero crossing of current.

When a breaker interrupts the small magnetising current of an unloaded transformer, the arc is weak. The current may be forced to zero (chopped) at an instantaneous value ii before its natural zero. The energy then trapped in the transformer inductance produces a switching overvoltage.

Mechanism

  CB (opens, chops i)
 ---/ ---+-----------+
         |           |
         C          L  (magnetising
     (winding +      |   inductance)
      bushing)       |
 --------+-----------+--- ground

At the chopping instant:

  • Current in the magnetising inductance =i= i. Magnetic energy =12Li2= \tfrac12 L i^2.
  • Voltage on the stray capacitance =v= v. Electric energy =12Cv2= \tfrac12 C v^2.

After the breaker opens, LL and CC form a closed oscillating circuit. The inductor current cannot change suddenly, so it charges CC. Energy swings between LL and CC at f=1/(2πLC)f = 1/(2\pi\sqrt{LC}), often a few hundred Hz to a few kHz. The peak voltage VmV_m is reached when all the energy is in CC:

12CVm2=12Li2+12Cv2\frac12 CV_m^2 = \frac12 Li^2 + \frac12 Cv^2 Vm=v2+LCi2V_m = \sqrt{v^2 + \frac{L}{C}i^2}

Effect of the chopping instant

The magnetising current lags the voltage by about 90∘90^\circ. With i=Imsin⁡θi = I_m\sin\theta at the chopping angle θ\theta, the capacitor voltage is v=Vpcos⁡θv = V_p\cos\theta, where VpV_p is the system peak voltage.

Chopping at the current peak (θ=90∘\theta = 90^\circ): i=Imi = I_m, v=0v = 0.

Vm=ImLCV_m = I_m\sqrt{\frac{L}{C}}

This is the maximum overvoltage. L/C\sqrt{L/C} is of the order of tens of kΩ, so it can be several times the system voltage.

Interruption at current zero (θ=0\theta = 0): i=0i = 0, so the magnetic energy 12Li2=0\tfrac12Li^2 = 0. Then

Vm=v2+0=v=VpV_m = \sqrt{v^2 + 0} = v = V_p

No extra energy is released. The voltage across the transformer does not exceed the normal system peak, and it simply decays through losses. The overvoltage is minimum (zero excess) when interruption takes place at the natural current zero.

Example: L=5L = 5 H, C=0.01 μC = 0.01\ \muF, so L/C=22.36\sqrt{L/C} = 22.36 kΩ. Chopping at 10 A gives 223.6 kV. Interrupting at current zero gives no overvoltage.

Remedies

  • Breakers with low chopping current. Vacuum and SF6_6 breakers are designed to interrupt near the natural zero.
  • Resistance switching across the contacts to damp the oscillation.
  • Surge arresters or RC snubbers at the transformer terminals.

✓ Answer checked by Claude Opus 5.5 (high effort)

All High Voltage Engineering chapter 3 questions →