Maximum switching overvoltage derivation
Short answer
Differentiating Vc(t) gives sinωt=0, so the first maximum occurs at t=π/ω; substituting gives Vmax=E+(E−V0)e^(−απ/ω), up to 2E with no trapped charge or 3E when V0=−E. Increasing R increases damping and lowers Vmax; increasing L reduces damping and raises Vmax; increasing C slightly lowers Vmax.
Starting from the expression for switching voltage as: Vc(t) = (E − V0)[1 − e^(−αt) (√(α² + ω²)/ω) cos(ωt − φ)] + V0, where tan φ = α/ω. Derive the expression for maximum switching over voltage magnitude and condition for it. Also discuss the effect of increasing R, L and C in the maximum switching over voltage.
For energising a lumped series –– line model with a step voltage and initial (trapped) capacitor voltage , the capacitor voltage is
with and .
Condition for maximum
Let , so and . Differentiate:
Setting gives , so The first (largest) maximum is at
Maximum switching overvoltage
At : , so
Special cases:
- No trapped charge (): , up to when .
- Trapped charge of opposite polarity (, as in fast reclosing): , up to when .
- : no overvoltage.
So the overvoltage is maximum when (i) the breaker closes at the peak of source voltage (so the step is the peak), (ii) the line holds a trapped charge of opposite polarity, and (iii) damping is small.
Effect of R, L and C
The damping exponent can be written as
- Increasing R: increases, falls, so decreases. For the circuit is overdamped and there is no overshoot (). This is why closing (pre-insertion) resistors are used.
- Increasing L: increases, falls (and falls), so damping reduces and increases. The oscillation also becomes slower.
- Increasing C: decreases, rises; is unchanged but falls, so the peak occurs later after more decay, and decreases slightly; the period becomes longer.
In real lines is small, so the damping factor is close to 1 and overvoltages of 2–3 pu occur unless resistors or arresters are used.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Switching overvoltage with trapped charge and Rs · High Voltage Engineering, chapter 3 · asked 3×
- Causes of switching overvoltage; inductive current interruption · High Voltage Engineering, chapter 3
- True/false: cables suppress switching overvoltage · High Voltage Engineering, chapter 3
- Overvoltage due to chopping of magnetising current · High Voltage Engineering, chapter 3
- Closing resistance Rs to limit overvoltage to 1.8 pu · High Voltage Engineering, chapter 3
- Direct lightning stroke overvoltage and tower footing · High Voltage Engineering, chapter 3
- T/F: switching overvoltage, lossless vs lossy · Transmission and Distribution System Design, chapter 3
- Triple product for r = a cos t i + a sin t j + at tanα k · Mathematics, chapter 5
- Increasing voltage vs increasing circuits · Transmission and Distribution System Design, chapter 2
- Maximum torque condition and T-s curves for different voltages · Electrical Machines I, chapter 5