Short answer

Major causes: energizing/reclosing long lines, interrupttion of small inductive or capacitive currents, fault clearing, load rejection, and ferroresonance. Interrupting inductive current causes overvoltage by current chopping: the magnetic energy ½Li₀² transfers to the stray capacitance, giving Vm = i₀√(L/C), which can restrike and escalate voltage.

What are the major causes of switching over voltages? Explain how interruption of inductive current causes over voltage.

Switching overvoltages are transient overvoltages produced when breakers or switches change the network configuration. They are the most important overvoltages for EHV and UHV lines (above about 400 kV), where they set the insulation levels.

Major causes

  1. Energising (closing) a long unloaded line. The step voltage starts travelling waves that double at the open end. With trapped charge from an earlier opening, the overvoltage can reach about 3 pu.
  2. High-speed reclosing on a line with trapped charge.
  3. Interruption of small inductive currents. Transformer magnetising current or reactor current is chopped before its natural zero.
  4. Interruption of capacitive currents. De-energising unloaded lines, cables or capacitor banks can cause restrikes and voltage escalation.
  5. Fault initiation and fault clearing, including out-of-phase switching.
  6. Load rejection, together with the Ferranti effect and generator overspeed. (Usually counted as a temporary overvoltage.)
  7. Ferroresonance during single-pole switching of unloaded transformers.

Overvoltage due to interruption of inductive current

When a breaker opens an unloaded transformer or reactor, the current is small (a few amperes). The arc becomes unstable and the breaker may cut the current abruptly at a value i0i_0 before its natural zero. This is current chopping.

  Vs ~--- CB ---+-----------+
            i0  |           |
               C stray     L (transformer)
                |           |
  --------------+-----------+--- ground
  • At the instant of chopping, the magnetic energy in the transformer inductance is 12Li02\tfrac{1}{2} L i_0^2.
  • The current in LL cannot change suddenly, so it flows into the stray capacitance CC of the winding and bushing. Energy oscillates between LL and CC at
f=12πLCf = \frac{1}{2\pi\sqrt{LC}}
  • When all the energy is in CC:
12CVm2=12Li02+12CV02\tfrac{1}{2} C V_m^2 = \tfrac{1}{2} L i_0^2 + \tfrac{1}{2} C V_0^2

where V0V_0 is the capacitor voltage at the chopping instant. When V0V_0 is small:

Vm≈i0LCV_m \approx i_0 \sqrt{\frac{L}{C}}

The surge impedance L/C\sqrt{L/C} of a transformer is very high (tens of kΩ). So chopping only 5–10 A can produce more than 200 kV.

Effects: the high voltage appears across the breaker contacts and can cause restrikes, with the voltage escalating, and it stresses the transformer insulation.

Remedies:

  • Resistance switching: a resistor across the breaker contacts damps the oscillation and absorbs the energy.
  • Surge arresters at the transformer terminals.
  • Breakers designed with low chopping levels.

✓ Answer checked by Claude Opus 5.5 (high effort)

All High Voltage Engineering chapter 3 questions →