- 2071 Magh · 3+3 marks
Feeder switching guideline; contactor in place of CB
Short answer
To disconnect a feeder: open CB first, then line and bus isolators, then earth it. To connect: remove earths, close isolators, then CB last. A contactor cannot replace the CB because it cannot interrupt fault currents and lacks relay tripping; it is only for frequent load switching with fuse backup.
A [high?] voltage feeder has a circuit breaker and isolator. Develop a guideline for connecting and disconnecting the feeder through isolator and circuit breaker. Can you replace circuit breaker with contactor in the feeder? Justify your answer.
Taking the question as a high-voltage feeder (e.g. 33 kV) fed from a bus through isolators and a circuit breaker.
Bus ==+==
|
[I1] bus isolator
|
[CB]
|
[I2] line isolator --[ES] earth switch
|
Feeder
Guideline for disconnecting the feeder
- Inform the control room and load end; reduce load if possible.
- Open the circuit breaker by the control switch; confirm "OFF" on the indicator and ammeter reading zero.
- Open the line isolator I2, then the bus isolator I1 (no-load operation).
- Check visibly that all three blades are open.
- Test for absence of voltage, then close the earth switch ES (and apply portable earths at the work site).
- Lock the isolators and CB, and attach "Do not operate – men at work" tags (permit-to-work).
Guideline for connecting the feeder
- Cancel the work permit; make sure all persons and portable earths are removed.
- Open the earth switch ES.
- Check that the CB is open; close the bus isolator I1, then the line isolator I2.
- Close the circuit breaker last; watch the ammeter and relay flags. If a fault exists, the CB trips safely.
- Record the operation in the log book.
Rule to remember: CB opens first and closes last; isolators move only when the CB is open. Interlocking enforces this.
Can a contactor replace the circuit breaker?
No, not on an HV feeder. Reasons:
- A contactor is built to make and break normal load currents (and motor starting currents), with breaking capacity of only about 8–10 times rated current. A feeder short circuit can be tens of kA; the contactor would fail to interrupt it and could weld or explode.
- A contactor has no tripping by protective relays in the usual sense; it opens only when the coil is de-energised, and it also drops out on voltage dips, causing unwanted outages.
- Contactors are mostly made for LV and up to about 11 kV (vacuum contactors); they do not have the voltage rating, insulation level or making capacity of a 33 kV CB.
- A contactor needs back-up fuses for short circuits; HV fuses large enough for a feeder are not practical and must be replaced after each fault.
A contactor is suitable only for frequent switching of a motor or capacitor bank; the feeder needs a circuit breaker with relays to clear faults.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Isolator operation with CB in HV installation · Switchgear and Protection, chapter 4
- Isolator vs CB and why both used · Switchgear and Protection, chapter 4 · asked 4×
- Contactor construction and remote control circuit · Switchgear and Protection, chapter 4
- IDMT settings for 20 MVA transformer and feeder · Switchgear and Protection, chapter 7 · asked 2×
- Vacuum circuit breaker · Switchgear and Protection, chapter 6 · asked 2×
- SF6 circuit breaker · Switchgear and Protection, chapter 6 · asked 2×
- Short circuit MVA of feeder circuit breaker · Power System Analysis II, chapter 3 · asked 2×
- Reactor to protect circuit breaker of small station · Power Plant Equipment, chapter 4
- T/F: switching surge ratio vs system voltage · Transmission and Distribution System Design, chapter 3 · asked 4×
- Switching resistance Rs for 1.8 pu limit · High Voltage Engineering, chapter 3 · asked 3×