- 2078 Chaitra · 6 marks
Contactor construction and remote control circuit
Short answer
A contactor uses an electromagnetic coil to close main contacts and a spring to open them. For remote control, Start buttons are wired in parallel and Stop buttons in series; a hold-in auxiliary contact maintains the coil after start is released, providing no-volt protection.
Explain the construction and operating principle of contactor. Draw the circuit diagram for remote control of a contactor.
A contactor is an electrically operated switch in which a magnetic coil closes the main contacts and a spring opens them when the coil is de-energised. It is used for frequent on-load switching and remote control of motors and other loads.
Construction
- Coil and laminated core (electromagnet), AC cores with a shading ring.
- Armature carrying the moving contacts through an insulated carrier.
- Main contacts (normally 3 NO, silver alloy) for the power circuit.
- Auxiliary contacts (NO/NC) for latching, interlocking and indication.
- Return spring, arc chutes/splitters, moulded housing and terminals.
Operating principle
- Control voltage on the coil produces flux; the armature is attracted against the spring.
- Main contacts close and the load is energised; auxiliary contacts change state.
- Removing coil voltage lets the spring open the contacts; the arc is extinguished in the arc chute at current zero.
- Since the coil drops out at low voltage, the contactor also gives no-volt protection.
Circuit for remote control of a contactor
START buttons are connected in parallel and STOP buttons in series, so the motor can be started or stopped from the local panel or from a distant point. The hold-in auxiliary contact K is connected in parallel with the START buttons. Only thin control wires go to the remote station.
L --[Fuse]--[STOP local]--[STOP remote]--+--------------+--------------+
(NC) (NC) | | |
[START local] [START remote] [K aux NO]
(NO) (NO) (hold)
| | |
+--------------+--------------+
|
[OL relay NC]
|
( K coil )
|
N ------------------------------------------------------+
Power: L1,L2,L3 -> fuses -> K main -> OL -> Motor
Working of the remote scheme
- Pressing any START button energises coil K; the main contacts close and the motor runs.
- The auxiliary contact K (in parallel with the START buttons) closes and holds the coil after the button is released.
- Pressing any STOP button opens the series path; the coil drops out and the motor stops.
- The overload relay NC contact also opens the coil path on overload.
- Indicating lamps through auxiliary contacts show ON/OFF status at the remote point.
This arrangement allows control of large motors (pumps, fans, cranes) from a control room using low-power control wiring, and safe automatic disconnection on overload or supply failure.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Construction and principle of contactor · Switchgear and Protection, chapter 4
- Contactor for motor control and protection · Switchgear and Protection, chapter 4 · asked 3×
- Isolator construction, principle and application · Switchgear and Protection, chapter 4
- Feeder switching guideline; contactor in place of CB · Switchgear and Protection, chapter 4
- Data logger and remote control block diagrams · Basic Electronics Engineering, chapter 7
- Report on road construction in remote Nepal · Communication English, chapter 9
- Remote control or digital multimeter · Basic Electronics Engineering, chapter 7
- Transformer operating principle and emf equation · Electrical Machines I, chapter 2 · asked 6×