Construction and principle of contactor
Short answer
A contactor contains an electromagnet (coil, laminated core with shading ring), an armature carrying silver‑alloy main and auxiliary contacts, a return spring, and arc chutes. Energising the coil attracts the armature, closing the contacts; de‑energising releases the spring to open them and extinguish the arc.
Explain the construction and operating principle of contactor.
A contactor is an electromagnetically operated switch used to make and break a power circuit many times, under normal load conditions, by a small control signal. It is used for motors, heaters, lighting and capacitor banks.
Construction
+------------------------+
| fixed contacts (3) |
| == == == |
| moving contacts |
| -- -- -- <- bridge |
| [ armature ] |
| ^ spring |
| [ coil on core ] |
+------------------------+
A1 A2 = coil terminals
- Electromagnet (coil and core): a laminated E- or U-shaped iron core with a coil. The coil works on AC or DC (24 V, 110 V, 230 V, 415 V). AC cores carry a shading ring to stop chatter.
- Armature: the movable iron part attracted by the magnet; the moving contacts are fixed to it through an insulating carrier.
- Main contacts (power contacts): usually three NO poles, made of silver alloy (silver–cadmium oxide or silver–tin oxide) for low resistance and resistance to welding. Double-break bridge contacts are common.
- Auxiliary contacts: small NO and NC contacts for holding, interlocking and signalling.
- Return spring: opens the contacts when the coil is de-energised.
- Arc chutes / arc splitters: splitter plates or blow-out coils in larger contactors cool and lengthen the arc.
- Enclosure and frame: moulded insulating housing with terminals.
Operating principle
- When the control voltage is applied to the coil, current in the coil sets up flux in the core.
- The magnetic pull exceeds the spring force; the armature moves and closes the main contacts (and changes over the auxiliary contacts). The load is connected.
- The coil current is small compared to the load current, so a small switch or PLC output can control a large load.
- When the coil is de-energised (STOP button, overload relay or supply failure), flux collapses and the spring opens the contacts. The arc formed is quenched in the arc chute at the next current zero.
- Because pick-up needs about 85% and drop-out happens below about 60–70% of coil voltage, a contactor gives built-in no-volt protection.
Main features
- Designed for very high mechanical life (millions of operations) and frequent switching.
- Breaking capacity is limited to a few times rated current (overload/motor stall current), not short-circuit current; fuses or MCCBs give short-circuit back-up.
- Utilisation categories (IEC 60947-4-1) such as AC-1 (resistive), AC-3 (squirrel-cage motor start and run), AC-4 (inching, plugging) define the duty.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Contactor construction and remote control circuit · Switchgear and Protection, chapter 4
- Isolator construction, principle and application · Switchgear and Protection, chapter 4
- Contactor for motor control and protection · Switchgear and Protection, chapter 4 · asked 3×
- Transformer operating principle and emf equation · Electrical Machines I, chapter 2 · asked 6×
- Servo motor operating principle · Electrical Machine, chapter 7 · asked 2×
- Capacitor start motor operating principle · Electric Machines II, chapter 3 · asked 2×
- Operating principle of 3-phase induction motor · Electrical Machines I, chapter 5