Short answer

On 10,000 kVA base, A and B parallel give 25.26%, and C is 7.5%. To keep fault level ≤150,000 kVA, total reactance must be 6.667%, so add a reactor of 1.56% (≈0.017 Ω) in series with the new generator.

A small generating station has two alternators of 2500KVA and 500KVA with percentage reactance of 8 & 6 percentage respectively. The circuit breakers are rated at 150,000kVA. Due to increase in system load it is intended to add a third generator of 10,000kVA rating and 7.5% reactance. If the system voltage is 3300volts, find the reactance X necessary to protect the C.B. [Figure: alternators A and B connected directly to the busbar, which feeds an outgoing circuit through the CB rated 150,000 kVA; the third generator C (10,000 kVA, 7.5%) is connected to the busbar through the reactor X]

The C.B. must not see a fault level above its rating (150,000 kVA). G3 is connected to the bus through reactor XX. For a fault on the outgoing circuit just beyond the C.B., all three machines feed the fault.

Base: 10,000 kVA, 3.3 kV; Zbase=3.3210=1.089 ΩZ_{base} = \dfrac{3.3^2}{10} = 1.089\ \Omega. Percentage reactance on new base: %Xnew=%X×kVAbkVA\%X_{new} = \%X\times\dfrac{\text{kVA}_b}{\text{kVA}}.

   A 2500kVA   B 500kVA    C 10000kVA,7.5%
     8%          6%          |
     |           |          [X]
 ====+===========+===========+==== 3.3 kV
           |
          CB 150,000 kVA
           |--- F

Reactances on 10,000 kVA base

MachineCalculation%X
A8×10000/25008\times10000/250032 %
B6×10000/5006\times10000/500120 %
Cgiven7.5 %

A∥BA\parallel B: 32×120152=25.263 %\dfrac{32\times120}{152} = 25.263\ \%, giving fault kVA =10000×100/25.263=39,583= 10000\times100/25.263 = 39{,}583 kVA (safe).

If C were connected directly: 25.263∥7.5=5.783 %25.263\parallel7.5 = 5.783\ \%, fault kVA =172,917= 172{,}917 kVA > 150,000 kVA. So a reactor is needed.

Required reactor

Allowed total reactance:

%Xeq=10000×100150000=6.667 %\%X_{eq} = \frac{10000\times100}{150000} = 6.667\ \% 16.667=125.263+17.5+X0.15−0.039583=0.110417=17.5+X7.5+X=9.0566X=1.5566 %\begin{aligned} \frac{1}{6.667} &= \frac{1}{25.263} + \frac{1}{7.5+X} \\ 0.15 - 0.039583 &= 0.110417 = \frac{1}{7.5+X} \\ 7.5 + X &= 9.0566 \\ X &= 1.5566\ \% \end{aligned}

In ohms:

XΩ=1.5566100×1.089=0.01695 ΩX_\Omega = \frac{1.5566}{100}\times1.089 = 0.01695\ \Omega

Answer: Reactor XX ≈ 1.557 % on 10,000 kVA base ≈ 0.017 Ω in series with the new generator keeps the fault level at 150,000 kVA.