- 2076 Chaitra · 5 marks
Reactor to protect circuit breaker of small station
Short answer
On 10,000 kVA base, A and B parallel give 25.26%, and C is 7.5%. To keep fault level ≤150,000 kVA, total reactance must be 6.667%, so add a reactor of 1.56% (≈0.017 Ω) in series with the new generator.
A small generating station has two alternators of 2500KVA and 500KVA with percentage reactance of 8 & 6 percentage respectively. The circuit breakers are rated at 150,000kVA. Due to increase in system load it is intended to add a third generator of 10,000kVA rating and 7.5% reactance. If the system voltage is 3300volts, find the reactance X necessary to protect the C.B. [Figure: alternators A and B connected directly to the busbar, which feeds an outgoing circuit through the CB rated 150,000 kVA; the third generator C (10,000 kVA, 7.5%) is connected to the busbar through the reactor X]
The C.B. must not see a fault level above its rating (150,000 kVA). G3 is connected to the bus through reactor . For a fault on the outgoing circuit just beyond the C.B., all three machines feed the fault.
Base: 10,000 kVA, 3.3 kV; . Percentage reactance on new base: .
A 2500kVA B 500kVA C 10000kVA,7.5%
8% 6% |
| | [X]
====+===========+===========+==== 3.3 kV
|
CB 150,000 kVA
|--- F
Reactances on 10,000 kVA base
| Machine | Calculation | %X |
|---|---|---|
| A | 32 % | |
| B | 120 % | |
| C | given | 7.5 % |
: , giving fault kVA kVA (safe).
If C were connected directly: , fault kVA kVA > 150,000 kVA. So a reactor is needed.
Required reactor
Allowed total reactance:
In ohms:
Answer: Reactor ≈ 1.557 % on 10,000 kVA base ≈ 0.017 Ω in series with the new generator keeps the fault level at 150,000 kVA.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Fault current: two 500 kVA alternators · Power Plant Equipment, chapter 4
- Fault current: two 50 MVA generators, feeder reactor · Power Plant Equipment, chapter 4 · asked 3×
- Feeder reactor: 40 and 30 MVA, 50% reduction · Power Plant Equipment, chapter 4 · asked 4×
- Feeder reactor: 40 and 30 MVA, 40% reduction · Power Plant Equipment, chapter 4 · asked 4×
- Function of reactor in power system · Power Plant Equipment, chapter 4 · asked 3×
- Bus-bar reactor scheme: 30 MVA and 50 MVA · Power Plant Equipment, chapter 4 · asked 2×
- DC supply system in a generating station · Power Plant Design, chapter 4
- Percentage increase with parallel pipe at midpoint · Hydraulics, chapter 2
- Short circuit MVA of feeder circuit breaker · Power System Analysis II, chapter 3 · asked 2×
- Reactance diagram: 300 MVA, 20 kV generator, two motors · Power System Analysis I, chapter 3