Isolator vs CB and why both used
Short answer
An isolator is an off‑load switch providing a visible break, while a CB makes/breaks load and fault currents. An isolator is needed because CB contacts are not visible and for CB maintenance; the two are used together with the CB interrupting current before the isolator opens, interlocked for safety.
What are the basic differences between isolator and circuit breaker? Although CB can be used to isolate the circuit, why do we need isolator? With a neat circuit diagram, explain why we use isolator and circuit breaker simultaneously in power system.
An isolator is an off-load disconnecting switch that gives a visible open gap so that a section of the circuit can be safely isolated for maintenance. A circuit breaker (CB) is an on-load switching device that can make, carry and break normal as well as fault currents automatically.
Differences between isolator and circuit breaker
| Point | Isolator | Circuit breaker |
|---|---|---|
| Operation | Off-load only (no current) | On-load and under fault |
| Arc quenching | No arc quenching medium | Has medium (oil, air, SF6, vacuum) |
| Fault interruption | Cannot break fault current | Breaks fault currents automatically |
| Control | Manual or motorised; not tripped by relay | Tripped by protective relays |
| Contact gap | Visible open gap | Contacts inside enclosure, not visible |
| Cost and size | Cheap, simple | Costly, complex mechanism |
| Purpose | Safety isolation for maintenance | Switching and protection |
Why an isolator is still needed
- The contacts of a CB are inside a tank or chamber; the open position is not visible, so the maintenance crew cannot be sure the circuit is dead.
- The CB itself needs maintenance (contact replacement, oil or gas filling). It must be isolated from both sides, which the CB cannot do for itself.
- An open CB still has a small gap; a long, visible air gap from an isolator, plus an earthing switch, gives a proven safe condition.
- Isolators are cheap, so they can be put at many points to section a bus or a feeder.
Using isolator and CB together
Bus ---[ I1 ]---[ CB ]---[ I2 ]--- Feeder/line
|
[ES] earth switch
|
===
I1, I2 = isolators on both sides of CB
Opening sequence (to isolate):
- Open the CB first; it breaks the load or fault current.
- Then open isolator I2 (line side) and I1 (bus side) at no load.
- Close the earth switch on the dead section.
Closing sequence (to restore):
- Open the earth switch.
- Close the isolators I1 and I2 (no current flows because CB is open).
- Finally close the CB to energise the feeder.
Isolators are interlocked with the CB so that they cannot be operated while the CB is closed. In this way the CB does the switching under load and fault, and the isolator gives safe, visible isolation; each covers what the other cannot do.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Isolator operation with CB in HV installation · Switchgear and Protection, chapter 4
- Vacuum circuit breaker · Switchgear and Protection, chapter 6 · asked 2×
- SF6 circuit breaker · Switchgear and Protection, chapter 6 · asked 2×
- Puffer type SF6 circuit breaker · Switchgear and Protection, chapter 6
- Air blast circuit breaker · Switchgear and Protection, chapter 6
- Minimum oil circuit breaker · Switchgear and Protection, chapter 6
- Why do we need DFT · Digital Signal Analysis and Processing, chapter 7 · asked 6×
- Short circuit MVA of feeder circuit breaker · Power System Analysis II, chapter 3 · asked 2×
- Basic structure of power system · Power System Analysis I, chapter 1
- Why do we need FFT · Digital Signal Analysis and Processing, chapter 7 · asked 2×