- 2075 Baisakh · 2+4 marks
Isolator operation with CB in HV installation
Short answer
An isolator is an off-load switch giving a visible gap. In HV, a CB is flanked by two isolators. Opening sequence: open CB first, then line and bus isolators; closing sequence: close isolators first, then CB. Interlocks enforce this order to prevent arcing.
What is isolator? With the single line diagram, explain the working of isolator with consideration of closing and opening of circuit breaker kept in high voltage installation.
Isolator
An isolator (disconnector) is an off-load mechanical switch that separates a part of the circuit from the live supply and gives a visible open gap for safe maintenance. It has no arc-quenching device, so it is opened or closed only when the circuit carries no current.
Working of isolator with the circuit breaker
In HV installations a CB is always placed between two isolators, with an earth switch on the line side.
HV Bus
|
[I1] bus-side isolator
|
[CB] circuit breaker
|
[I2] line-side isolator
|-----[ES] earth switch --- earth
|
Outgoing line / transformer
Opening (taking the feeder out of service):
- Open the circuit breaker first. It interrupts the load current and quenches the arc in its medium.
- Now no current flows, so open isolator I2 (line side) and then I1 (bus side).
- Close the earth switch ES to earth the dead feeder and drain trapped charge.
- Lock and tag the isolators; work can now be done safely on the CB or the line.
Closing (putting the feeder in service):
- Open the earth switch ES.
- Close isolator I1 and then I2; since the CB is open, they close without current.
- Close the circuit breaker last; it makes the load current (and, if there is a fault, the fault current, after which it trips).
Why this order is important
- If an isolator is opened while the CB is closed, it breaks load current and draws a long arc, which can burn the contacts, cause phase-to-phase flashover and endanger the operator.
- The CB is designed to make and break current; the isolator only gives isolation.
- Interlocks (mechanical keys or electrical) between the CB, isolators and earth switch enforce this sequence: isolators can move only when the CB is open, and the earth switch can close only when the isolators are open.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Isolator vs CB and why both used · Switchgear and Protection, chapter 4 · asked 4×
- HVDC circuit breaker operation · Switchgear and Protection, chapter 6
- Vacuum circuit breaker · Switchgear and Protection, chapter 6 · asked 2×
- SF6 circuit breaker · Switchgear and Protection, chapter 6 · asked 2×
- Air blast circuit breaker · Switchgear and Protection, chapter 6
- Minimum oil circuit breaker · Switchgear and Protection, chapter 6
- Design: 310 m head plant, HV breaker · Power Plant Design, chapter 4 · asked 3×
- Opening and closing a data file · Computer Programming, chapter 10 · asked 2×
- Quotation for HV breaker of a 48 MW plant · Power Plant Design, chapter 4
- Closing resistance Rs to limit overvoltage to 1.8 pu · High Voltage Engineering, chapter 3