River crossing: minimum clearance above water
Short answer
The vertex of the conductor lies 16.7 m outside the span toward the 40 m tower, so the lowest point in the span is at that tower. Minimum clearance to water is therefore 40 m.
A transmission line conductor at a river crossing is supported from two towers at height of 40 m and 60 m above water level. The horizontal distance between the towers is 300 meters. Find the minimum clearance between the conductor and water level. Assume maximum working tension in conductor is 3000 kg and conductor weight = 1200 kg/km.
For supports at unequal heights, the lowest point of the conductor is first located. If it falls outside the span, the minimum clearance occurs at the lower support.
Data: m, m, kg, kg/km kg/m.
Position of the lowest point
Let be the horizontal distance from the lowest point to the lower tower, and the distance to the higher tower.
Since is negative, the vertex of the parabola lies 16.67 m outside the span, beyond the 40 m tower.
Check: m, which equals .
60 m
___--o
___---`` |
vertex 40 m ___-- |
. ___--o`` |
<-16.7-> | <------ 300 m --->|
~~~~~~~~~~~~|~~~~~~ water ~~~~~~~~|~~~
Minimum clearance
Within the span, the conductor rises continuously from the 40 m tower to the 60 m tower. The vertex would be only m below the lower support level, but it lies outside the span. So the lowest point actually on the conductor is at the lower support.
The tower heights are taken as the heights of the conductor attachment points.
Answer: the minimum clearance between the conductor and the water is 40 m, at the lower tower. There is no sag dip within the span, because the vertex falls 16.7 m outside it.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Minimum clearance, towers at 45 m and 70 m · Transmission and Distribution System Design, chapter 4
- Economical span, 200 km, 10% angle towers · Transmission and Distribution System Design, chapter 4 · asked 2×
- Conductor tension in stringing condition · Transmission and Distribution System Design, chapter 4
- Economical span, double circuit, A/B/C towers · Transmission and Distribution System Design, chapter 4 · asked 5×
- Most economical span, double circuit line · Transmission and Distribution System Design, chapter 4 · asked 6×
- Conductor tension under varying conditions · Transmission and Distribution System Design, chapter 4
- Pipe outlet minimum water level, 50 lps · Irrigation and Drainage Engineering, chapter 7
- Charging current of 60 Hz horizontal 132 kV line · Power System Analysis I, chapter 4
- Two-wire 40 Ω line, input and output voltage · Electromagnetism, chapter 5
- Short note: river crossing alternatives · Transportation Engineering I, chapter 5
All Transmission and Distribution System Design chapter 4 questions →