- 2069 Bhadra (old course) · 10 marks
Conductor tension in stringing condition
Short answer
Using the stringing equation, the stringing tension at 25°C without wind/ice is found from the toughest condition (UTS/2.5=6364 kg, wind+ice). The required tension is 2211 kg, giving a sag of about 8.78 m.
Taking the factor of safety under toughest condition to be 2.5, compute the tension in the conductor to be given in the conductor for stringing condition for a span of 300 m. Assume the ultimate tensile strength of a conductor is 15910 kg and factor of safety of 2.5. Use the following data: The conductor specifications are: Area = 462.60 mm², Linear expansion coefficient α = 17.73×10⁻⁶/°C, Modulus of elasticity (E) = 0.789×10⁶ kg/cm², Weight (Wc) = 1726 kg/km, Radius = 1.40 cm.
| Condition | Temperature | Wind pressure | Ice loading (ice density 950 kg/m³) |
|---|---|---|---|
| Toughest condition | −5°C | 100 kg/m² | 1 cm |
| Stringing condition | 25°C | - | - |
[Given stringing equation: T2²[T2 + K2] − K1 = 0, where K2 = −T1 + α(θ2 − θ1)AE + W1²L²AE/(24T1²) and K1 = W2²L²AE/24.]
The stringing tension is found by solving the given stringing equation from the toughest condition (−5°C, wind and ice) to the stringing condition (25°C, still air).
Toughest condition (condition 1)
Allowable tension:
Conductor diameter cm; ice thickness cm.
Stringing condition (condition 2)
kg/m, C.
Constants
Solving
By trial (or Newton's method):
| (kg) | |
|---|---|
| 2000 | (too low) |
| 2200 | (slightly low) |
| 2211.2 | (matches) |
Check: the stringing sag is m. The sag in the toughest condition is m.
Answer: the conductor should be strung with a tension of about 2211 kg (about 13.9% of UTS) at 25°C, giving a stringing sag of about 8.78 m on the 300 m span.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Sag and tension in easiest condition · Transmission and Distribution System Design, chapter 4
- Conductor tension under varying conditions · Transmission and Distribution System Design, chapter 4
- Most economical span from sag table · Transmission and Distribution System Design, chapter 4 · asked 2×
- T/F: maximum sag in stringing condition · Transmission and Distribution System Design, chapter 4
- Economical span, 200 km, 10% angle towers · Transmission and Distribution System Design, chapter 4 · asked 2×
- Most economical span, double circuit line · Transmission and Distribution System Design, chapter 4 · asked 6×
- Drainage rate: 300 mm in 3 days, growth factor 1.5 · Irrigation and Drainage Engineering, chapter 9 · asked 2×
- Ultimate strength of ISA 100x100x10, M20 bolts · Design of Steel and Timber Structure, chapter 5
- Tensile test data of a steel bar · Material Science, chapter 3
- Splitting tensile strength of cylinder and cube (500 kN) · Concrete Technology and Masonry Structure, chapter 5 · asked 2×
All Transmission and Distribution System Design chapter 4 questions →