- 2067 Chaitra (old course) · 8 marks
Sag and tension in easiest condition
Short answer
Using the change-of-state equation from the toughest condition (tension 4000 kg, resultant weight 2.171 kg/m) to the easiest (60 °C, no wind), the tension is solved as 1728 kg. Maximum vertical sag = 0.844×300²/(8×1728) = 5.49 m.
Evaluate the maximum sag and tension in easiest condition for a transmission line of span 300 m with following data: Conductor: cross-section: 226 mm²; Diameter: 20 mm; Weight: 0.844 kg/m; UTS: 8000 kg.
| Parameter | Toughest condition | Easiest condition |
|---|---|---|
| Temperature | 0°C | 60°C |
| Wind pressure | 100 kg/m² | 0 |
| Tension | UTS/2 | ? |
| Ice thickness | 0 | 0 |
The tension in the easiest condition is found from the change-of-state (stringing) equation, starting from the toughest condition. The maximum (vertical) sag then follows.
Assumed (not given): kg/cm² and /°C, the usual values for ACSR.
Toughest condition (1): 0°C, wind 100 kg/m²
Easiest condition (2): 60°C, no wind
kg/m, C, and
Stringing equation
Solve :
| (kg) | LHS |
|---|---|
| 1700 | |
| 1750 | |
| 1728.3 | ✓ |
Maximum sag (easiest condition)
For comparison, the sag in the toughest condition is m. That sag is inclined, at , so its vertical component is only m. The easiest condition therefore gives the largest vertical sag.
Answer: in the easiest condition the tension is about 1728 kg (21.6% of UTS) and the maximum vertical sag is about 5.49 m.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Most economical span from sag table · Transmission and Distribution System Design, chapter 4 · asked 2×
- Most economical EHV span from sag table · Transmission and Distribution System Design, chapter 4 · asked 2×
- Conductor tension in stringing condition · Transmission and Distribution System Design, chapter 4
- T/F: maximum sag in stringing condition · Transmission and Distribution System Design, chapter 4
- Economical span, 200 km, 10% angle towers · Transmission and Distribution System Design, chapter 4 · asked 2×
- Most economical span, double circuit line · Transmission and Distribution System Design, chapter 4 · asked 6×
- Maximum power over 20 + j50 Ω line · Power System Analysis I, chapter 6
- Maximum power over 20 + j30 Ω line · Power System Analysis I, chapter 6
- True length of 780 m line, tape 0.693 kg · Surveying I, chapter 2 · asked 2×
- Interior cross wall design: stiffened, 130 mm slab · Concrete Technology and Masonry Structure, chapter 8
All Transmission and Distribution System Design chapter 4 questions →