Using Ryle's formula for tower weight based on bending moment from wind load and tower height (sag + ground clearance), the 250 m span yields the lowest tower steel weight per km (8.50 t/km), making it the most economical span.

For the design of most economical span of an extra high voltage transmission line, following data are available for a particular conductor. Select the most economical span. Given that: conductor diameter = 21 mm, conductor cross sectional area = 262 mm², conductor UTS = 9127 kg, Wind pressure = 100 kg/m².

Span (m)Maximum sag (m)
2504.36
2755.22
3006.04
3256.89
3507.81

[Figure: conductor arrangement/air clearance on the tower — three conductors with vertical spacing of 3 m between the top and middle and 3 m between the middle and bottom; the top and bottom conductors on one side and the middle conductor on the other, with a horizontal width of 9 m across.] Assume: All towers are straight line towers. The air clearance is shown in figure. Minimum ground clearance is 10 m. Neglect the effect of ground wire.

The most economical span is the one with the least tower weight (cost) per km. Tower heights come from the ground clearance plus the sag, and the loads are wind only, because all towers are straight-line towers (θ = 0).

Tower heights

From the figure, the vertical spacing is 3 m between the top and middle conductors and 3 m between the middle and bottom conductors. The ground wire is neglected, so the top conductor sets the tower height.

h1=ground clearance+Dmax=10+Dmaxh2=h1+3,h3=Ht=h1+6\begin{aligned} h_1 &= \text{ground clearance} + D_{max} = 10 + D_{max}\\ h_2 &= h_1 + 3, \qquad h_3 = H_t = h_1 + 6 \end{aligned}

Bending moment

The wind load on each conductor, with the wind span equal to the span, is

F=p d L=100×0.021×L=2.1L kgF = p\,d\,L = 100\times0.021\times L = 2.1L\ \text{kg} M=F(h1+h2+h3)M = F(h_1+h_2+h_3)

There is no deviation (straight-line towers), so the conductor tension adds no transverse load. The UTS and area are therefore not needed for this comparison; they only fix the sag values, which are already given.

Tower weight

Tower weight is taken from Ryle's formula (as given with IOE papers):

Wt=0.0016 HtM×FS  tonneW_t = 0.0016\,H_t\sqrt{M\times FS}\ \ \text{tonne}

Here HtH_t is in ft, MM is the bending moment at the base in klb-ft, and FS = 2 (assumed). The conversions are 1 m = 3.281 ft and 1 kg·m = 0.007233 klb-ft. Tower cost is taken as proportional to tower weight, and the number of towers per km is about 1000/L1000/L. So the span with the least tower weight per km is the most economical.

Sample (L = 250 m):

h1=14.36, h2=17.36, h3=20.36 mM=525×(14.36+17.36+20.36)=27,342 kg⋅mWt=0.0016×(20.36×3.281)27342×0.007233×2=2.126 tWeight/km=2.126×4=8.502 t/km\begin{aligned} h_1 &= 14.36,\ h_2 = 17.36,\ h_3 = 20.36\ \text{m}\\ M &= 525\times(14.36+17.36+20.36) = 27{,}342\ \text{kg·m}\\ W_t &= 0.0016\times(20.36\times3.281)\sqrt{27342\times0.007233\times2} = 2.126\ \text{t}\\ \text{Weight/km} &= 2.126\times4 = 8.502\ \text{t/km} \end{aligned}

Results

Span (m)Sag (m)h1h_1 (m)h2h_2 (m)h3=Hth_3=H_t (m)F per cond. (kg)M (kg·m)WtW_t (t)Weight/km (t)
2504.3614.3617.3620.36525.027,3422.12568.5022
2755.2215.2218.2221.22577.531,5662.38038.6557
3006.0416.0419.0422.04630.035,9862.63978.7990
3256.8916.8919.8922.89682.540,7252.91658.9737
3507.8117.8120.8123.81735.045,8863.22029.2005

As the span increases, the sag (and so the tower height) and the wind load both rise. The tower weight increases faster than the number of towers per km falls, so the weight per km rises with span.

Answer: the most economical span is 250 m (8.50 t/km of tower steel). In practice this is checked against fixed per-tower costs (foundations, insulators, erection), which favour somewhat longer spans.

✓ Answer checked by Claude Opus 5.5 (high effort)