Interior cross wall design: stiffened, 130 mm slab

Short answer

230 mm thick wall; slenderness ratio 9.55 (ks=0.903), ground storey stress 0.211 N/mm², required basic compressive stress 0.233 N/mm². Use bricks of at least 5 N/mm² with M2 (1:6) mortar.

Design an interior cross-wall of a two-storeyed building to carry 130 mm thick RCC slab with ceiling height of 2.8 m, and the wall is 3.2 m long which is stiffened and supports a 2 m slab on both sides as shown in the figure. Assume all necessary data relevant to Nepal code. [Figure: cross section of wall - 2000 mm slab span on each side, 130 mm thick RCC slabs, 2.8 m storey height for two storeys, on foundation.]

Data and assumptions

  • Design code: IS 1905:1987; NBC 109 follows the same permissible-stress method.
  • Interior cross wall 230 mm thick (one brick, Nepal practice), modular bricks, kp=1k_p=1. Brick masonry 19 kN/m3^3, RCC 25 kN/m3^3.
  • Stated slab width is taken as the tributary width of slab per metre run of wall (each side contributing half of its span). Finish applies to roof and floors; live load not reduced.
  • Sections are checked at the base of each storey (wall height for weight = clear ceiling height).
  • Wall 3.2 m long and stiffened by cross walls at its ends (effective length 1.0L=3.21.0L=3.2 m, Table 5), which is greater than hefh_{ef}, so height governs the slenderness. Slab 130 mm, ceiling 2.8 m, slab span 2.0 m each side (tributary 2.0 m).
  • Finish 1.0 kN/m2^2, live load 1.5 kN/m2^2 (roof) and 2.0 kN/m2^2 (floor) assumed as per IS 875 Part 2 for residential use.

Step 1: Loads per metre run of wall

Unit weights (IS 875 Part 1): RCC 25 kN/m3^3, brick masonry 19 kN/m3^3.

ItemWorkingkN/m
Slab dead + finish25×0.130+1.0=4.25025\times0.130 + 1.0 = 4.250 kN/m2^2-
Roof slab reaction(4.250+1.5)×2.0(4.250 + 1.5)\times2.011.50
Floor slab reaction(4.250+2.0)×2.0(4.250 + 2.0)\times2.012.50
Wall per storey0.23×2.80×190.23\times2.80\times1912.24

Step 2: Slenderness ratio and factors

Interior wall with slabs on both sides: load is axial (e=0e=0, IS 1905 App. A-4). RCC slab bearing on the wall gives full restraint (Table 4 Sl. 1): hef=0.75Hh_{ef}=0.75H, with H=2.80+0.130=2.930H=2.80+0.130=2.930 m.

hef=0.75×2.930=2.197 mSR=2.1970.23=9.55 (<27)\begin{aligned} h_{ef} &= 0.75\times2.930 = 2.197\ \text{m}\\ SR &= \frac{2.197}{0.23} = 9.55\ (<27) \end{aligned}

ks=0.903k_s = 0.903 (Table 9, e=0e=0, interpolated), ka=1.0k_a = 1.0 (area 0.23 m2^2/m ≥0.2\ge 0.2), kp=1.0k_p=1.0.

Step 3: Stress and required fbf_b at the base of each storey

SectionLoad NN (kN/m)σ=N/(t×1000)\sigma=N/(t\times1000) (N/mm²)Required fb=σ/(kskakp)f_b=\sigma/(k_sk_ak_p) (N/mm²)
Top (2nd) storey base23.740.1030.114
Ground storey base48.470.2110.233

Step 4: Brick strength and mortar (IS 1905 Table 8)

Smallest standard unit strength for each section:

SectionRequired fbf_bM2 (1:6)M1 (1:5)H2 (1:4)
Top (2nd) storey base0.1143.53.53.5
Ground storey base0.2333.53.53.5

Answer: 230 mm thick wall; the ground storey governs, requiring 3.5 N/mm2^2 brick with M2 (1:6) mortar (required fb=0.233f_b=0.233 N/mm2^2; fbf_b provided 0.35). The same brick and mortar can be used throughout. As a practical minimum, adopt bricks of not less than 5 N/mm2^2 with 1:6 cement mortar (SR = 9.55 < 27, OK).