- 2074 Chaitra · 9 marks
Interior cross wall design: stiffened, 130 mm slab
Short answer
230 mm thick wall; slenderness ratio 9.55 (ks=0.903), ground storey stress 0.211 N/mm², required basic compressive stress 0.233 N/mm². Use bricks of at least 5 N/mm² with M2 (1:6) mortar.
Design an interior cross-wall of a two-storeyed building to carry 130 mm thick RCC slab with ceiling height of 2.8 m, and the wall is 3.2 m long which is stiffened and supports a 2 m slab on both sides as shown in the figure. Assume all necessary data relevant to Nepal code. [Figure: cross section of wall - 2000 mm slab span on each side, 130 mm thick RCC slabs, 2.8 m storey height for two storeys, on foundation.]
Data and assumptions
- Design code: IS 1905:1987; NBC 109 follows the same permissible-stress method.
- Interior cross wall 230 mm thick (one brick, Nepal practice), modular bricks, . Brick masonry 19 kN/m, RCC 25 kN/m.
- Stated slab width is taken as the tributary width of slab per metre run of wall (each side contributing half of its span). Finish applies to roof and floors; live load not reduced.
- Sections are checked at the base of each storey (wall height for weight = clear ceiling height).
- Wall 3.2 m long and stiffened by cross walls at its ends (effective length m, Table 5), which is greater than , so height governs the slenderness. Slab 130 mm, ceiling 2.8 m, slab span 2.0 m each side (tributary 2.0 m).
- Finish 1.0 kN/m, live load 1.5 kN/m (roof) and 2.0 kN/m (floor) assumed as per IS 875 Part 2 for residential use.
Step 1: Loads per metre run of wall
Unit weights (IS 875 Part 1): RCC 25 kN/m, brick masonry 19 kN/m.
| Item | Working | kN/m |
|---|---|---|
| Slab dead + finish | kN/m | - |
| Roof slab reaction | 11.50 | |
| Floor slab reaction | 12.50 | |
| Wall per storey | 12.24 |
Step 2: Slenderness ratio and factors
Interior wall with slabs on both sides: load is axial (, IS 1905 App. A-4). RCC slab bearing on the wall gives full restraint (Table 4 Sl. 1): , with m.
(Table 9, , interpolated), (area 0.23 m/m ), .
Step 3: Stress and required at the base of each storey
| Section | Load (kN/m) | (N/mm²) | Required (N/mm²) |
|---|---|---|---|
| Top (2nd) storey base | 23.74 | 0.103 | 0.114 |
| Ground storey base | 48.47 | 0.211 | 0.233 |
Step 4: Brick strength and mortar (IS 1905 Table 8)
Smallest standard unit strength for each section:
| Section | Required | M2 (1:6) | M1 (1:5) | H2 (1:4) |
|---|---|---|---|---|
| Top (2nd) storey base | 0.114 | 3.5 | 3.5 | 3.5 |
| Ground storey base | 0.233 | 3.5 | 3.5 | 3.5 |
Answer: 230 mm thick wall; the ground storey governs, requiring 3.5 N/mm brick with M2 (1:6) mortar (required N/mm; provided 0.35). The same brick and mortar can be used throughout. As a practical minimum, adopt bricks of not less than 5 N/mm with 1:6 cement mortar (SR = 9.55 < 27, OK).
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Cross wall design, 120 mm slab, 3 m wide · Concrete Technology and Masonry Structure, chapter 8 · asked 4×
- Cross wall design, 125 mm slab, 3.2 m · Concrete Technology and Masonry Structure, chapter 8 · asked 3×
- Cross wall design, 120 mm slab, 3.0 m · Concrete Technology and Masonry Structure, chapter 8 · asked 2×
- Interior cross wall design: three-storey, 150 mm slab · Concrete Technology and Masonry Structure, chapter 8 · asked 2×
- Single-storey external wall: stress, brick, mortar · Concrete Technology and Masonry Structure, chapter 8
- Interior slab design, 4x5 m · Design of RCC Structure, chapter 9
- Two-room building: brick plinth, door shutters, plaster · Estimating and Costing, chapter 6
- Two-way slab on RCC beams, 4x6 m · Design of RCC Structure, chapter 9 · asked 2×
- Building: brick 1:6, ceiling plaster, PCC · Estimating and Costing, chapter 6
All Concrete Technology and Masonry Structure chapter 8 questions →