Cross wall design, 125 mm slab, 3.2 m
Short answer
230 mm thick interior cross wall, effective height 2.494 m, slenderness ratio 10.84. Required basic compressive stress 0.292 N/mm²; adopt bricks of crushing strength not less than 3.5 N/mm² with M2 mortar (1:6 cement:sand).
Design an interior cross wall of a two-storeyed building to carry 125 mm thick RCC slab with 3.2 m ceiling height. The wall is unstiffened and supports a 2.5 m wide slab on both sides. Assume necessary data relevant to Nepal. Live load on roof = 1.5 kN/m; live load on floor = 2.0 kN/m; floor finishing = 1.2 kN/m. [Figure: brick wall between slabs with 3200 mm storey heights, on a floor.]
Data and assumptions
- Design code: IS 1905:1987; NBC 109 follows the same permissible-stress method.
- Interior cross wall 230 mm thick (one brick, Nepal practice), modular bricks, . Brick masonry 19 kN/m, RCC 25 kN/m.
- Stated slab width is taken as the tributary width of slab per metre run of wall (each side contributing half of its span). Finish applies to roof and floors; live load not reduced.
- Sections are checked at the base of each storey (wall height for weight = clear ceiling height).
- Wall unstiffened, so slenderness is governed by height. Slab 125 mm, ceiling height 3.2 m, tributary width 2.5 m.
Step 1: Loads per metre run of wall
Unit weights (IS 875 Part 1): RCC 25 kN/m, brick masonry 19 kN/m.
| Item | Working | kN/m |
|---|---|---|
| Slab dead + finish | kN/m | - |
| Roof slab reaction | 14.56 | |
| Floor slab reaction | 15.81 | |
| Wall per storey | 13.98 |
Step 2: Slenderness ratio and factors
Interior wall with slabs on both sides: load is axial (, IS 1905 App. A-4). RCC slab bearing on the wall gives full restraint (Table 4 Sl. 1): , with m.
(Table 9, , interpolated), (area 0.23 m/m ), .
Step 3: Stress and required at the base of each storey
| Section | Load (kN/m) | (N/mm²) | Required (N/mm²) |
|---|---|---|---|
| Top (2nd) storey base | 28.55 | 0.124 | 0.143 |
| Ground storey base | 58.34 | 0.254 | 0.292 |
Step 4: Brick strength and mortar (IS 1905 Table 8)
Smallest standard unit strength for each section:
| Section | Required | M2 (1:6) | M1 (1:5) | H2 (1:4) |
|---|---|---|---|---|
| Top (2nd) storey base | 0.143 | 3.5 | 3.5 | 3.5 |
| Ground storey base | 0.292 | 3.5 | 3.5 | 3.5 |
Answer: 230 mm thick wall; the ground storey governs, requiring 3.5 N/mm brick with M2 (1:6) mortar (required N/mm; provided 0.35). The same brick and mortar can be used throughout. As a practical minimum, adopt bricks of not less than 5 N/mm with 1:6 cement mortar (SR = 10.84 < 27, OK).
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Cross wall design, 120 mm slab, 3 m wide · Concrete Technology and Masonry Structure, chapter 8 · asked 4×
- Interior cross wall design: stiffened, 130 mm slab · Concrete Technology and Masonry Structure, chapter 8
- Cross wall design, 120 mm slab, 3.0 m · Concrete Technology and Masonry Structure, chapter 8 · asked 2×
- Interior cross wall design: three-storey, 150 mm slab · Concrete Technology and Masonry Structure, chapter 8 · asked 2×
All Concrete Technology and Masonry Structure chapter 8 questions →