Interior cross wall design: three-storey, 150 mm slab
Short answer
230 mm interior wall, mortar H2 (1:4), slenderness ratio 11.90. Minimum brick crushing strengths: top storey 3.5 N/mm², second storey 5 N/mm², ground storey 7.5 N/mm². The whole wall may be built with 7.5 N/mm² bricks for simplicity.
Design an interior cross wall of a three-storied building to carry 150 mm thick RCC slab with ceiling height of 3.5 m. The wall supports a 3.0 m wide slab. Take live load on roof = 2 kN/m, live load on floors = 3.5 kN/m, floor finishes = 1.5 kN/m. [Figure: cross section along the interior wall - three storeys of 3.5 m height each between RCC slabs, mortar 1:4 in all storeys, wall resting on a foundation, slab width 3.0 m.]
Data and assumptions
- Design code: IS 1905:1987; NBC 109 follows the same permissible-stress method.
- Interior cross wall 230 mm thick (one brick, Nepal practice), modular bricks, . Brick masonry 19 kN/m, RCC 25 kN/m.
- The stated slab width is taken as the tributary width of slab per metre run of wall (each side contributing half of its span). The finish applies to the roof and floors; live load is not reduced.
- Sections are checked at the base of each storey (wall height for self weight = clear ceiling height).
- Mortar 1:4 cement:sand = grade H2 (IS 1905 Table 1) in all storeys.
Step 1: Loads per metre run of wall
Unit weights (IS 875 Part 1): RCC 25 kN/m, brick masonry 19 kN/m.
| Item | Working | kN/m |
|---|---|---|
| Slab dead + finish | kN/m | - |
| Roof slab reaction | 21.75 | |
| Floor slab reaction | 26.25 | |
| Wall per storey | 15.30 |
Step 2: Slenderness ratio and factors
Interior wall with slabs on both sides: the load is axial (, IS 1905 App. A-4). An RCC slab bearing on the wall gives full restraint (Table 4 Sl. 1): , with m.
(Table 9, , interpolated), (area 0.23 m/m ), .
Step 3: Stress and required at the base of each storey
| Section | Load (kN/m) | (N/mm²) | Required (N/mm²) |
|---|---|---|---|
| Top (3rd) storey | 37.05 | 0.161 | 0.191 |
| 2nd storey | 78.59 | 0.342 | 0.406 |
| Ground (1st) storey | 120.14 | 0.522 | 0.620 |
Step 4: Brick strength and mortar (IS 1905 Table 8)
Mortar fixed as H2 (cement:sand 1:4):
| Section | Required | Brick strength (N/mm²) | provided |
|---|---|---|---|
| Top (3rd) storey | 0.191 | 3.5 | 0.35 |
| 2nd storey | 0.406 | 5 | 0.50 |
| Ground (1st) storey | 0.620 | 7.5 | 0.74 |
Answer: 230 mm wall, mortar H2 (1:4). Minimum brick strength: top storey 3.5 N/mm, second storey 5 N/mm, ground storey 7.5 N/mm (slenderness ratio 11.90 < 27 in all storeys). For simplicity, the whole wall may be built with 7.5 N/mm bricks in H2 mortar, which also gives extra safety in the upper storeys.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Cross wall design, 120 mm slab, 3 m wide · Concrete Technology and Masonry Structure, chapter 8 · asked 4×
- Interior cross wall design: stiffened, 130 mm slab · Concrete Technology and Masonry Structure, chapter 8
- Cross wall design, 125 mm slab, 3.2 m · Concrete Technology and Masonry Structure, chapter 8 · asked 3×
- Cross wall design, 120 mm slab, 3.0 m · Concrete Technology and Masonry Structure, chapter 8 · asked 2×
- Single-storey external wall: stress, brick, mortar · Concrete Technology and Masonry Structure, chapter 8
- Brick and mortar for 230 mm wall (100 kN/m) · Concrete Technology and Masonry Structure, chapter 8 · asked 7×
- Design T-beam with 150 mm slab · Design of RCC Structure, chapter 4
- Capitalized value of three-storied RCC building · Construction Management, chapter 13
- Multi-storey wall: stresses at each level · Design of Timber and Masonry Structures, chapter 5
- Interior slab design, 4x5 m · Design of RCC Structure, chapter 9
All Concrete Technology and Masonry Structure chapter 8 questions →