Multi-storey wall: stresses at each level

Short answer

Stresses at base: top 0.122 N/mm², middle 0.288 N/mm², ground 0.454 N/mm² (permissible 0.448). Ground storey fails; redesign to 345 mm thick wall reduces stress to 0.321 N/mm² (< 0.49 N/mm²).

A three-storey load-bearing brick wall has a uniform thickness of 230 mm in all storeys; each storey height is 3.0 m with RC slabs at each floor and roof level giving lateral and rotational restraint at both ends of the wall in each storey. The roof slab transfers 15 kN/m and each of the two floor slabs transfers 25 kN/m (working loads, including live load). Unit weight of masonry is 19 kN/m³. The basic compressive stress for the masonry is fb=0.5f_b = 0.5 N/mm². Find the stress at the base of each storey and check against the permissible stress (take ksk_s for SR 8 → 0.95, SR 10 → 0.89). If the ground storey fails, redesign its thickness as 345 mm.

Step 1: Permissible stress

Each storey is fixed at both ends: Heff=0.75×3000=2250H_{eff} = 0.75 \times 3000 = 2250 mm.

SR=2250230=9.78,ks=0.89+0.222×0.06=0.897SR = \frac{2250}{230} = 9.78, \quad k_s = 0.89 + \frac{0.22}{2}\times 0.06 = 0.897

Area per metre =0.23= 0.23 m² >0.2> 0.2, so ka=1.0k_a = 1.0, kp=1.0k_p = 1.0:

fc=0.5×0.897=0.448 N/mm2f_c = 0.5 \times 0.897 = 0.448\ \text{N/mm}^2

Step 2: Self-weight per storey

Ws=19×0.23×3.0=13.11 kN/mW_{s} = 19 \times 0.23 \times 3.0 = 13.11\ \text{kN/m}

Step 3: Loads and stresses at each base level

Level (base of)RoofFloorsWall self-weightTotal (kN/m)Stress (N/mm²)PermissibleCheck
Top storey15013.1128.110.1220.448Safe
Middle storey15252×13.11=26.222 \times 13.11 = 26.2266.220.2880.448Safe
Ground storey15503×13.11=39.333 \times 13.11 = 39.33104.330.4540.448Slightly over

Stress =load/(230×1000)= \text{load}/(230 \times 1000).

The ground storey stress exceeds the permissible value by about 1 percent, so it is not acceptable.

Step 4: Redesign of the ground storey with 345 mm wall

Self-weight of the 345 mm ground wall =19×0.345×3.0=19.67= 19 \times 0.345 \times 3.0 = 19.67 kN/m. Load at base:

P=15+50+2×13.11+19.67=110.89 kN/mP = 15 + 50 + 2 \times 13.11 + 19.67 = 110.89\ \text{kN/m} SR=2250345=6.52,ks≈0.99fc=0.5×0.99=0.49 N/mm2f=110 890345×1000=0.321 N/mm2<0.49\begin{aligned} SR &= \frac{2250}{345} = 6.52, \quad k_s \approx 0.99 \\ f_c &= 0.5 \times 0.99 = 0.49\ \text{N/mm}^2 \\ f &= \frac{110\,890}{345 \times 1000} = 0.321\ \text{N/mm}^2 < 0.49 \end{aligned}

A 345 mm wall at the ground storey is safe (stress ratio 0.65). The 230 mm upper wall should sit centrally on the 345 mm wall (57.5 mm projection on each side) so that the load stays concentric. If it were flush with one face, the eccentricity of 57.5 mm would add large bending stress and the check above would no longer hold.

Answer: Stresses at base: top 0.122, middle 0.288, ground 0.454 N/mm² (permissible 0.448). The ground storey needs a 345 mm wall (stress 0.321 N/mm² < 0.49).