- Practice · 8 marks
Multi-storey wall: stresses at each level
Short answer
Stresses at base: top 0.122 N/mm², middle 0.288 N/mm², ground 0.454 N/mm² (permissible 0.448). Ground storey fails; redesign to 345 mm thick wall reduces stress to 0.321 N/mm² (< 0.49 N/mm²).
A three-storey load-bearing brick wall has a uniform thickness of 230 mm in all storeys; each storey height is 3.0 m with RC slabs at each floor and roof level giving lateral and rotational restraint at both ends of the wall in each storey. The roof slab transfers 15 kN/m and each of the two floor slabs transfers 25 kN/m (working loads, including live load). Unit weight of masonry is 19 kN/m³. The basic compressive stress for the masonry is N/mm². Find the stress at the base of each storey and check against the permissible stress (take for SR 8 → 0.95, SR 10 → 0.89). If the ground storey fails, redesign its thickness as 345 mm.
Step 1: Permissible stress
Each storey is fixed at both ends: mm.
Area per metre m² , so , :
Step 2: Self-weight per storey
Step 3: Loads and stresses at each base level
| Level (base of) | Roof | Floors | Wall self-weight | Total (kN/m) | Stress (N/mm²) | Permissible | Check |
|---|---|---|---|---|---|---|---|
| Top storey | 15 | 0 | 13.11 | 28.11 | 0.122 | 0.448 | Safe |
| Middle storey | 15 | 25 | 66.22 | 0.288 | 0.448 | Safe | |
| Ground storey | 15 | 50 | 104.33 | 0.454 | 0.448 | Slightly over |
Stress .
The ground storey stress exceeds the permissible value by about 1 percent, so it is not acceptable.
Step 4: Redesign of the ground storey with 345 mm wall
Self-weight of the 345 mm ground wall kN/m. Load at base:
A 345 mm wall at the ground storey is safe (stress ratio 0.65). The 230 mm upper wall should sit centrally on the 345 mm wall (57.5 mm projection on each side) so that the load stays concentric. If it were flush with one face, the eccentricity of 57.5 mm would add large bending stress and the check above would no longer hold.
Answer: Stresses at base: top 0.122, middle 0.288, ground 0.454 N/mm² (permissible 0.448). The ground storey needs a 345 mm wall (stress 0.321 N/mm² < 0.49).
✓ Answer checked by Claude Sonnet 5.5
Related questions
- Check of a solid brick wall under gravity load · Design of Timber and Masonry Structures, chapter 5
- Wall with openings: pier loads and check · Design of Timber and Masonry Structures, chapter 5
- Distribution of lateral force among masonry walls · Design of Timber and Masonry Structures, chapter 6
- Wall subjected to an eccentric load · Design of Timber and Masonry Structures, chapter 5
- Effective height, thickness and slenderness ratio · Design of Timber and Masonry Structures, chapter 5
- Out-of-plane bending of a masonry wall · Design of Timber and Masonry Structures, chapter 6
- Interior cross wall design: three-storey, 150 mm slab · Concrete Technology and Masonry Structure, chapter 8 · asked 2×
- Brick and mortar for 230 mm wall (100 kN/m) · Concrete Technology and Masonry Structure, chapter 8 · asked 7×
- Single-storey external wall: stress, brick, mortar · Concrete Technology and Masonry Structure, chapter 8
- Load bearing wall: crushing strength and mortar · Concrete Technology and Masonry Structure, chapter 8
All Design of Timber and Masonry Structures chapter 5 questions →