- 2078 Kartik · 12 marks
Single-storey external wall: stress, brick, mortar
Short answer
Maximum stress 0.66 N/mm². Required basic compressive stress 0.57 N/mm². Use bricks of crushing strength not less than 7.5 N/mm² with M2 mortar (cement:sand 1:6), giving permissible stress 0.59 N/mm².
An external wall of a single storeyed building is 23 cm thick and carries 100 kN/m load at the top of the wall with an eccentricity of 12 mm. The plinth level is 1.5 m above the top of foundation footing and floor to ceiling height is 3.0 m. The RCC slab bears on the wall and is 12 cm thick. Determine the maximum stress in the wall and calculate the strength of brick and grade of mortar required for the wall. Assume necessary data if any required.
Data and assumptions
- Wall 230 mm thick, modular bricks (); load at top 100 kN/m with eccentricity 12 mm, so ().
- Plinth 1.5 m above top of footing, ceiling height 3.0 m, 12 cm RCC slab bearing on the wall. Walls longer than (no cross walls given), so height governs.
- Brick masonry 19 kN/m. Design by IS 1905:1987; NBC 109 follows the same method. Critical section: base of wall at the top of the footing.
Step 1: Effective height and slenderness ratio
Height from top of footing to the centre of slab m (IS 1905 Table 4 Note 1). The footing and the RCC slab give full restraint, so :
Step 2: Load and maximum stress at the base
(At the top of the wall, under the load alone, N/mm.) The maximum stress in the wall is 0.656 N/mm at the base (compression; no tension since ).
Step 3: Factors and required basic stress
- (Table 9, , , interpolated)
- (area 0.23 m/m),
- : 25 percent increase allowed (cl. 5.4.1.4 a)
Step 4: Brick and mortar (IS 1905 Table 8)
| Mortar (IS 1905 Table 1) | Min. unit strength (N/mm²) | Table 8 (N/mm²) |
|---|---|---|
| M2 (cement:sand 1:6) | 7.5 | 0.59 |
| M1 (cement:sand 1:5) | 7.5 | 0.74 |
| H2 (cement:sand 1:4) | 7.5 | 0.74 |
| H1 (cement:sand 1:3) | 7.5 | 0.75 |
Answer: maximum stress = 0.656 N/mm. Required N/mm, so use bricks of crushing strength not less than 7.5 N/mm with M2 mortar (1:6, N/mm). A richer mortar (M1, H2, H1) also needs 7.5 N/mm units, so there is no gain from a stronger mortar here.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Brick and mortar for 23 cm wall (165 kN/m) · Concrete Technology and Masonry Structure, chapter 8 · asked 7×
- Brick and mortar for 230 mm wall (100 kN/m) · Concrete Technology and Masonry Structure, chapter 8 · asked 7×
- Wall with openings: stress, brick, mortar · Concrete Technology and Masonry Structure, chapter 8
- Brick and mortar for 250 mm wall (350 kN/m) · Concrete Technology and Masonry Structure, chapter 8 · asked 7×
- Single-room wall: brick strength and mortar · Concrete Technology and Masonry Structure, chapter 8
- Brick and mortar: 20 cm wall, 3.4 m · Concrete Technology and Masonry Structure, chapter 8 · asked 7×
- Two-room building: brick plinth, door shutters, plaster · Estimating and Costing, chapter 6
- Load bearing building: excavation, brick, plaster · Estimating and Costing, chapter 6
- Check of a solid brick wall under gravity load · Design of Timber and Masonry Structures, chapter 5
- Multi-storey wall: stresses at each level · Design of Timber and Masonry Structures, chapter 5
All Concrete Technology and Masonry Structure chapter 8 questions →