Brick and mortar for 250 mm wall (350 kN/m)
Short answer
Required basic compressive stress 1.37 N/mm². Use bricks of crushing strength not less than 17.5 N/mm² with H1 mortar (cement:sand 1:3); permissible stress 1.45 N/mm².
A wall 250 mm thick, using modular bricks, carries at the top a load of 350 kN/m having resultant eccentricity ratio of 1/12. The wall is 5 m long between cross walls and is 3.5 m clear height between RCC slabs at the top and bottom. What shall be the strength of brick and the grade of mortar? Assume that joints are not raked.
Data and assumptions
- Wall 250 mm thick, modular bricks, joints not raked. Load 350 kN/m at top, .
- Wall 5 m long between cross walls, clear height 3.5 m between RCC slabs (slab thickness not given, m).
- Note: a 350 kN/m load is high for brick masonry, so strong units are needed.
- Design code: IS 1905:1987 (Tables 4 to 10); NBC 109 follows the same permissible-stress method.
- Brick masonry unit weight 19 kN/m (IS 875 Part 1); modular brick, height/width , so .
Step 1: Effective height, length and slenderness ratio (IS 1905 cl. 4.3, 4.4, 4.6)
Height between slab centres m. Effective height m. Effective length (wall supported by a cross wall at each end, Table 5 Sl. 3) m. The lesser value governs:
Step 2: Design load per metre run at the base
Stress on the wall:
Step 3: Reduction factors
- Stress reduction factor (Table 9, , , by linear interpolation)
- Area reduction factor (cl. 5.4.1.2): area per metre 0.25 m is not less than 0.2 m, so
- Shape factor (modular bricks, height/width , Table 10)
- Since , a 25 percent increase in permissible stress is allowed (cl. 5.4.1.4 a), factor 1.25
Step 4: Required basic compressive stress
(Without the 25 percent increase the requirement would be N/mm.)
Step 5: Strength of brick and grade of mortar (IS 1905 Table 8)
Smallest standard unit strength giving N/mm:
| Mortar (IS 1905 Table 1) | Min. unit strength (N/mm²) | Table 8 (N/mm²) |
|---|---|---|
| M2 (cement:sand 1:6) | 30 | 1.51 |
| M1 (cement:sand 1:5) | 25 | 1.47 |
| H2 (cement:sand 1:4) | 20 | 1.41 |
| H1 (cement:sand 1:3) | 17.5 | 1.45 |
Answer: use bricks of crushing strength not less than 17.5 N/mm with mortar H1 (cement:sand 1:3) ( N/mm 1.372). Other combinations in the table are also acceptable; a stronger mortar allows a weaker brick.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Brick and mortar for 230 mm wall (100 kN/m) · Concrete Technology and Masonry Structure, chapter 8 · asked 7×
- Brick and mortar: 20 cm wall, 3.4 m · Concrete Technology and Masonry Structure, chapter 8 · asked 7×
- Brick and mortar for 23 cm wall (165 kN/m) · Concrete Technology and Masonry Structure, chapter 8 · asked 7×
- Brick and mortar for wall with timber flooring · Concrete Technology and Masonry Structure, chapter 8
- Brick and mortar: wall 175 kN/m, 4.2 m · Concrete Technology and Masonry Structure, chapter 8
- Single-room wall: brick strength and mortar · Concrete Technology and Masonry Structure, chapter 8
- Load bearing wall: crushing strength and mortar · Concrete Technology and Masonry Structure, chapter 8
- Single-storey external wall: stress, brick, mortar · Concrete Technology and Masonry Structure, chapter 8
- Wall with openings: stress, brick, mortar · Concrete Technology and Masonry Structure, chapter 8
- Check of a solid brick wall under gravity load · Design of Timber and Masonry Structures, chapter 5
All Concrete Technology and Masonry Structure chapter 8 questions →