- 2081 Baisakh · 10 marks
Brick and mortar: wall 175 kN/m, 4.2 m
Short answer
Required basic compressive stress 0.72 N/mm². Use bricks of crushing strength not less than 10 N/mm² with M2 mortar (cement:sand 1:6); permissible stress 0.81 N/mm².
A wall is 4.2 m long between cross walls and the clear height of the wall is 3.2 m between RCC slabs of 12 cm thick at top and bottom. The brick wall carries an eccentric load of 175 kN/m (eccentricity of loading at 1/12) inclusive of self weight. What should be the strength of brick and grade of mortar? Use Nepal Standard Brick and joints are not raked.
Data and assumptions
- Thickness not given: Nepal standard brick mm, so a one-brick wall of 230 mm is adopted (joints not raked). Load 175 kN/m inclusive of self weight, .
- Wall 4.2 m long between cross walls, clear height 3.2 m between 12 cm RCC slabs, so m.
- Design code: IS 1905:1987 (Tables 4 to 10); NBC 109 follows the same permissible-stress method.
- Brick masonry unit weight 19 kN/m (IS 875 Part 1); modular brick, height/width , so .
Step 1: Effective height, length and slenderness ratio (IS 1905 cl. 4.3, 4.4, 4.6)
Height between slab centres m. Effective height m. Effective length (wall supported by a cross wall at each end, Table 5 Sl. 3) m. The lesser value governs:
Step 2: Design load per metre run at the base
Load at the base (self weight already included) kN/m.
Stress on the wall:
Step 3: Reduction factors
- Stress reduction factor (Table 9, , , by linear interpolation)
- Area reduction factor (cl. 5.4.1.2): area per metre 0.23 m is not less than 0.2 m, so
- Shape factor (modular bricks, height/width , Table 10)
- Since , a 25 percent increase in permissible stress is allowed (cl. 5.4.1.4 a), factor 1.25
Step 4: Required basic compressive stress
(Without the 25 percent increase the requirement would be N/mm.)
Step 5: Strength of brick and grade of mortar (IS 1905 Table 8)
Smallest standard unit strength giving N/mm:
| Mortar (IS 1905 Table 1) | Min. unit strength (N/mm²) | Table 8 (N/mm²) |
|---|---|---|
| M2 (cement:sand 1:6) | 10 | 0.81 |
| M1 (cement:sand 1:5) | 7.5 | 0.74 |
| H2 (cement:sand 1:4) | 7.5 | 0.74 |
| H1 (cement:sand 1:3) | 7.5 | 0.75 |
Answer: use bricks of crushing strength not less than 10 N/mm with mortar M2 (cement:sand 1:6) ( N/mm 0.720). Other combinations in the table are also acceptable; a stronger mortar allows a weaker brick.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Brick and mortar for 23 cm wall (165 kN/m) · Concrete Technology and Masonry Structure, chapter 8 · asked 7×
- Brick and mortar: 20 cm wall, 3.4 m · Concrete Technology and Masonry Structure, chapter 8 · asked 7×
- Brick and mortar for 230 mm wall (100 kN/m) · Concrete Technology and Masonry Structure, chapter 8 · asked 7×
- Brick and mortar for 250 mm wall (350 kN/m) · Concrete Technology and Masonry Structure, chapter 8 · asked 7×
- Load bearing wall: crushing strength and mortar · Concrete Technology and Masonry Structure, chapter 8
- Single-room wall: brick strength and mortar · Concrete Technology and Masonry Structure, chapter 8
- Wall subjected to an eccentric load · Design of Timber and Masonry Structures, chapter 5
- Check of a solid brick wall under gravity load · Design of Timber and Masonry Structures, chapter 5
- Tubular column load and eccentric loading · Strength of Materials, chapter 10
All Concrete Technology and Masonry Structure chapter 8 questions →