- 2067 Mangsir (old course) · 6 marks
Minimum clearance, towers at 45 m and 70 m
Short answer
Minimum clearance is 45 m at lower tower TR1. With tension 4000 kg, the catenary vertex lies 244.9 m outside the span, so the conductor rises continuously and no sag occurs within the span.
A transmission line conductor of weight 0.844 kg/m and span 300 meters is supported from two towers TR1 and TR2 at the height of 45 m and 70 m respectively from a common reference. Find the minimum clearance of the conductor from reference.
For supports at unequal heights, first find where the lowest point of the conductor lies. If it falls outside the span, the lowest conductor point is at the lower tower.
Data: kg/m, m, m. The tension is not given. Assume the conductor is the same as in the companion question (UTS = 8000 kg, factor of safety 2), so kg.
Position of the lowest point
Measured from the lower tower TR1:
is negative, so the vertex lies 244.9 m outside the span, beyond TR1. Inside the span, the conductor rises continuously from TR1 (45 m) to TR2 (70 m).
TR2 o 70 m
__..--` |
TR1 __..--`` |
vertex 45 m o |
(outside) |<---- 300 m --->|
===== reference ===================
Generality of the result
The vertex lies inside the span only if
Any practical working tension is above 1519 kg, since it is usually 20–50% of UTS. So the result does not depend on the exact tension assumed.
Answer: the minimum clearance of the conductor from the reference is 45 m, at tower TR1. The conductor has no dip within the span, because its vertex falls about 245 m outside it (for T = 4000 kg).
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- River crossing: minimum clearance above water · Transmission and Distribution System Design, chapter 4
- Economical span, 200 km, 10% angle towers · Transmission and Distribution System Design, chapter 4 · asked 2×
- Most economical span, double circuit line · Transmission and Distribution System Design, chapter 4 · asked 6×
- Economical span, double circuit, A/B/C towers · Transmission and Distribution System Design, chapter 4 · asked 5×
- Conductor selection, 100 MW 70 km 132 kV · Transmission and Distribution System Design, chapter 4
- Most economical span from sag table · Transmission and Distribution System Design, chapter 4 · asked 2×
- Cable shape and length between two towers · Theory of Structures I, chapter 7
- Design simply supported beam, 6 m span · Design of RCC Structure, chapter 4
- Beam 4 m span, 45 kN/m and 100 kN midspan · Design of Steel and Timber Structure, chapter 7
- 70 km, 40 MW line: regulation and zero-regulation pf · Power System Analysis I, chapter 6
All Transmission and Distribution System Design chapter 4 questions →