70 km, 40 MW line: regulation and zero-regulation pf

Short answer

For the short line, voltage regulation is 9.47% and sending-end power factor is 0.753 lagging. To achieve zero regulation, the receiving-end power factor must be about 0.981 leading (exact 0.969 leading).

At the receiving end of a 70 km long transmission line a 40 MW load at 0.8 lagging power factor is connected at 66 kV. The series resistance and inductive reactance of the conductor per phase are 0.03 ohm/km and 0.15 ohm/km respectively. Calculate (i) voltage regulation of the line and sending end power factor (ii) receiving end power factor to make the voltage regulation zero.

Short line (70 km), shunt capacitance neglected.

Data

R=0.03×70=2.1 Ω,X=0.15×70=10.5 ΩVR=66 000/3=38 105.1 VI=40×1063×66 000×0.8=437.39∠−36.87∘ A\begin{aligned} R &= 0.03\times70 = 2.1\ \Omega,\quad X = 0.15\times70 = 10.5\ \Omega \\ V_R &= 66\,000/\sqrt3 = 38\,105.1\ \text{V} \\ I &= \frac{40\times10^6}{\sqrt3\times66\,000\times0.8} = 437.39\angle-36.87^\circ\ \text{A} \end{aligned}

(i) Regulation and sending-end pf

IZ=437.39∠−36.87∘×10.708∠78.69∘=4683.5∠41.82∘ VVS=38 105.1+4683.5∠41.82∘=41 712.5∠4.29∘ V\begin{aligned} IZ &= 437.39\angle-36.87^\circ\times10.708\angle78.69^\circ = 4683.5\angle41.82^\circ\ \text{V} \\ V_S &= 38\,105.1 + 4683.5\angle41.82^\circ = 41\,712.5\angle4.29^\circ\ \text{V} \end{aligned}

Line value =3×41.713=72.25= \sqrt3\times41.713 = 72.25 kV.

%VR=72.25−6666×100=9.47%\%VR = \frac{72.25 - 66}{66}\times100 = 9.47\%

Angle between VSV_S and II =4.29∘+36.87∘=41.16∘= 4.29^\circ + 36.87^\circ = 41.16^\circ:

pfS=cos⁡41.16∘=0.753 lagging\text{pf}_S = \cos41.16^\circ = 0.753\ \text{lagging}

(ii) Receiving-end pf for zero regulation

Approximate condition (leading pf):

IRcos⁡ϕ−IXsin⁡ϕ=0tan⁡ϕ=RX=2.110.5=0.2cos⁡ϕ=0.981 leading\begin{aligned} IR\cos\phi - IX\sin\phi &= 0 \\ \tan\phi &= \frac{R}{X} = \frac{2.1}{10.5} = 0.2 \\ \cos\phi &= 0.981\ \text{leading} \end{aligned}

(The exact condition ∣VS∣=∣VR∣|V_S| = |V_R| with PP = 40 MW gives Q=−10.13Q = -10.13 MVAr, i.e. pf 0.969 leading.)

Answer: (i) Regulation ≈ 9.47 %, sending-end pf ≈ 0.753 lag; (ii) receiving-end pf ≈ 0.981 leading (exact 0.969 leading).

✓ Answer checked by Claude Opus 5.5 (high effort)