Capacitor for zero regulation, 70 km 220 kV line

Short answer

To achieve zero regulation, a three-phase shunt capacitor of 87.8 MVAr is needed, corresponding to 5.77 µF per phase in star connection.

A 70 km long, 50 Hz, 3-phase overhead transmission line is operating at 220 kV. The series impedance of the line is 8 + j22 Ohm/phase. The line is supplying a load of 100 MW at 0.9 p.f. lagging. Compute the capacitance per phase to be connected across the load so as to make the voltage regulation of the line zero.

Short line: Z=8+j22 ΩZ = 8 + j22\ \Omega/phase, VRV_R = 220 kV, load 100 MW at 0.9 pf lag (QL=100tan⁡25.84∘=48.43Q_L = 100\tan25.84^\circ = 48.43 MVAr). Without compensation the regulation is 3.92 %.

Condition for zero regulation

With line kV and three-phase MW/MVAr, the net receiving-end P+jQP + jQ must satisfy ∣VS∣=∣VR∣|V_S| = |V_R|:

VS=VR+(R+jX)(P−jQ)VR∣VR∣4=(VR2+RP+XQ)2+(XP−RQ)2\begin{aligned} V_S &= V_R + \frac{(R + jX)(P - jQ)}{V_R} \\ |V_R|^4 &= (V_R^2 + RP + XQ)^2 + (XP - RQ)^2 \end{aligned}

Substituting VR=220V_R = 220, P=100P = 100, R=8R = 8, X=22X = 22:

48 4002=(48 400+800+22Q)2+(2200−8Q)248\,400^2 = (48\,400 + 800 + 22Q)^2 + (2200 - 8Q)^2 548Q2+2 129 600Q+82 920 000=0548Q^2 + 2\,129\,600Q + 82\,920\,000 = 0

Taking the root nearer zero:

Q=−39.34 MVAr(net pf=0.931 leading)Q = -39.34\ \text{MVAr}\quad(\text{net pf} = 0.931\ \text{leading})

Capacitor rating

QC=QL−Q=48.43+39.34=87.77 MVAr (3-phase)Q_C = Q_L - Q = 48.43 + 39.34 = 87.77\ \text{MVAr (3-phase)}

Capacitance per phase (star connected)

C=QCωVL2=87.77×106314.16×(220×103)2=5.77 μFC = \frac{Q_C}{\omega V_L^2} = \frac{87.77\times10^6}{314.16\times(220\times10^3)^2} = 5.77\ \mu\text{F}

(For a delta-connected bank, CΔ=C/3=1.92 μC_\Delta = C/3 = 1.92\ \muF.)

Using the approximate rule tan⁡ϕ=R/X\tan\phi = R/X leading gives QC=48.43+100(8/22)=84.80Q_C = 48.43 + 100(8/22) = 84.80 MVAr and CC ≈ 5.58 µF, close to the exact value.

Answer: About 87.8 MVAr of shunt capacitors, i.e. C ≈ 5.77 µF per phase (star).

✓ Answer checked by Claude Opus 5.5 (high effort)

All Power System Analysis I chapter 6 questions →