Conductor selection, 220 kV line for 200 MW

Short answer

Use twin ACSR Bear (30/7/3.35 mm), two sub‑conductors per phase at 400 mm spacing. Thermal rating 960 A > 583 A, corona voltage 206 kV > 141.5 kV, power angle 7.75° < 30°, regulation 11.6% < 12%. Single conductors fail the regulation limit.

For a transmission line to deliver 200 MW of power over 120 km, it has been decided to design a 220 kV transmission line of single circuit. Select the best suitable conductor and conductor composition which meets the following technical criterion. i) Satisfy the thermal rating ii) No corona in fair weather condition iii) Power angle between sending end and receiving end must be within 30° iv) Initial voltage regulation within 12%. [ACSR conductor table to be provided; not reproduced with this paper.]

The conductor must pass all four technical checks. The cheapest arrangement that passes is chosen.

Assumptions: pf 0.9 lagging at the receiving end, 220 kV at the receiving end; standard ACSR table (IOE); the tower geometry from the air-clearance design (adjacent phases 11.03 m apart, outer phases 9.77 m apart, so GMD = 10.59 m); medium line with the nominal-π model; δ=1\delta = 1, m=0.85m = 0.85; GMR=0.7788rGMR = 0.7788r; twin bundle spacing s=0.4s = 0.4 m.

i) Thermal rating

I=200×1063×220×103×0.9=583.2 AI = \frac{200\times10^6}{\sqrt3\times220\times10^3\times0.9} = 583.2\ \text{A}
  • Single conductor: Sheep (592 A) or larger.
  • Twin bundle: each sub-conductor carries 291.6 A, so Coyote/Tiger (about 311 A) or larger.

Checks on single conductors

Using x=2πf×2×10−4ln⁡(GMD/GMR)x = 2\pi f\times2\times10^{-4}\ln(GMD/GMR) Ω/km and Vs=AVr+BIrV_s = AV_r + BI_r:

ConductorX total (Ω)δ (°)Regulation (%)VcV_c phase (kV)
Sheep51.889.8716.04166.1
Deer51.379.9315.46175.9
Moose50.9110.0314.76185.3

Every single conductor fails the 12% regulation limit. The reactance (about 0.43 Ω/km) is too high. A twin bundle is needed to cut the reactance.

Checks on twin bundles

Bundle (2 per phase)X (Ω)R (Ω)δ (°)Regulation (%)VcV_c (kV)
2 × Tiger40.2713.217.2114.54151.4
2 × Lion39.157.287.7011.94196.8
2 × Bear38.956.567.7511.61206.0
2 × Goat38.575.357.8211.04225.1

2 × Lion only just passes, at 11.94%. With resistance at the operating temperature (about 10% higher), its regulation rises to about 12.2% and it fails. 2 × Bear is the smallest bundle with a safe margin.

Detailed check: twin ACSR Bear

Data: r=23.45/2=11.725r = 23.45/2 = 11.725 mm, R20=0.1093R_{20} = 0.1093 Ω/km per sub-conductor.

GMRb=0.7788r×s=0.009131×0.4=0.06044 mx=0.06283ln⁡10.5920.06044=0.3246 Ω/kmreq=rs=0.06848 m,b=2πf×2πε0ln⁡(GMD/req)=3.467 μS/kmZ=(0.1093/2)×120+j0.3246×120=6.558+j38.95 ΩY=j4.160×10−4 S,A=1+ZY2=0.99190∠0.08∘Vr=127.0∠0∘ kV,Ir=583.2∠−25.84∘ AVs=AVr+ZIr=139.33+j18.95 kV=140.61∠7.75∘ kV\begin{aligned} GMR_b &= \sqrt{0.7788r\times s} = \sqrt{0.009131\times0.4} = 0.06044\ \text{m}\\ x &= 0.06283\ln\frac{10.592}{0.06044} = 0.3246\ \Omega/\text{km}\\ r_{eq} &= \sqrt{rs} = 0.06848\ \text{m}, \quad b = \frac{2\pi f\times2\pi\varepsilon_0}{\ln(GMD/r_{eq})} = 3.467\ \mu\text{S/km}\\ Z &= (0.1093/2)\times120 + j0.3246\times120 = 6.558 + j38.95\ \Omega\\ Y &= j4.160\times10^{-4}\ \text{S}, \quad A = 1 + \frac{ZY}{2} = 0.99190\angle0.08^\circ\\ V_r &= 127.0\angle0^\circ\ \text{kV}, \quad I_r = 583.2\angle{-25.84^\circ}\ \text{A}\\ V_s &= AV_r + ZI_r = 139.33 + j18.95\ \text{kV} = 140.61\angle7.75^\circ\ \text{kV} \end{aligned}

i) Thermal: 2 × 480 = 960 A, which exceeds 583 A. Passes.

ii) Corona: for the bundle,

Vc≈21.1 m δ n rln⁡(GMD/req)1+(n−1)r/s=206.0 kV (phase)V_c \approx \frac{21.1\,m\,\delta\,n\,r\ln(GMD/r_{eq})}{1 + (n-1)r/s} = 206.0\ \text{kV (phase)}

This exceeds the 141.5 kV maximum phase voltage, so there is no fair-weather corona.

iii) Power angle: δ = 7.75°, which is below 30°.

iv) Regulation:

∣Vs∣/∣A∣−VrVr=140.61/0.9919−127.02127.02=11.61%\frac{|V_s|/|A| - V_r}{V_r} = \frac{140.61/0.9919 - 127.02}{127.02} = 11.61\%

This is below 12%. The sending-end voltage is 243.6 kV (line), within the 245 kV maximum.

Answer: use ACSR "Bear" (30/7/3.35 mm) in a twin bundle (2 sub-conductors per phase, 400 mm apart). This gives δ = 7.75°, regulation 11.6%, corona voltage 206 kV per phase and a 960 A rating. No single conductor can meet the 12% regulation limit at 0.9 pf.