33 kV, 12 MW leading load: efficiency, zero regulation

Short answer

Efficiency is 92.45%. To make voltage regulation zero, add about 0.2 MVAr of shunt capacitance at the load, resulting in a net receiving-end power factor of approximately 0.894 leading.

A 50 Hz, 3-phase, 33 kV overhead line is supplying a load of 12 MW at 0.9 p.f. leading. The line has a series impedance of 6 + j16 Ω/phase. Compute the efficiency of the transmission line. How can the voltage regulation of the line be made zero?

Short line: Z=6+j16 ΩZ = 6 + j16\ \Omega, VRV_R = 33 kV, load 12 MW at 0.9 pf leading.

Efficiency

I=12×1063×33 000×0.9=233.27 APloss=3I2R=3(233.27)2(6)=0.979 MWη=1212+0.979×100=92.45%\begin{aligned} I &= \frac{12\times10^6}{\sqrt3\times33\,000\times0.9} = 233.27\ \text{A} \\ P_{loss} &= 3I^2R = 3(233.27)^2(6) = 0.979\ \text{MW} \\ \eta &= \frac{12}{12 + 0.979}\times100 = 92.45\% \end{aligned}

Present regulation

VS=19 052.6+233.27∠25.84∘ (6+j16)=19 102.3∠11.99∘ V⇒33.09 kV (line),%VR=0.26%\begin{aligned} V_S &= 19\,052.6 + 233.27\angle25.84^\circ\,(6 + j16) = 19\,102.3\angle11.99^\circ\ \text{V} \\ &\Rightarrow 33.09\ \text{kV (line)},\quad \%VR = 0.26\% \end{aligned}

The regulation is already very small, because the leading load current nearly cancels the drop.

Making regulation zero

Zero regulation needs ∣VS∣=∣VR∣|V_S| = |V_R|. With line kV, MW, MVAr:

(VR2+RP+XQ)2+(XP−RQ)2=VR4(V_R^2 + RP + XQ)^2 + (XP - RQ)^2 = V_R^4 (1089+72+16Q)2+(192−6Q)2=10892(1089 + 72 + 16Q)^2 + (192 - 6Q)^2 = 1089^2

The root nearer zero is

Q=−6.01 MVAr(pf=0.894 leading)Q = -6.01\ \text{MVAr} \quad (\text{pf} = 0.894\ \text{leading})

The load supplies −12tan⁡25.84∘=−5.81-12\tan25.84^\circ = -5.81 MVAr, so a little more leading VAr is needed:

QC=6.01−5.81=0.20 MVArQ_C = 6.01 - 5.81 = 0.20\ \text{MVAr}

So connect a small shunt capacitor (about 0.2 MVAr, C=QC/ωVL2≈0.58 μC = Q_C/\omega V_L^2 \approx 0.58\ \muF per phase in star) at the receiving end, or raise the leading current of a synchronous load slightly. In general, regulation is made zero by adjusting receiving-end reactive power (capacitor or reactor) until the net pf is near cos⁡ϕ=X/∣Z∣\cos\phi = X/|Z| leading.

Note: the approximate rule tan⁡ϕ=R/X\tan\phi = R/X gives pf 0.936 lead here, but at such small regulation the neglected quadrature term matters, so the exact value above is used.

Answer: Efficiency ≈ 92.45 %. Regulation (now 0.26 %) becomes zero with about 0.2 MVAr of extra shunt capacitance at the load (net pf ≈ 0.894 leading).