33 kV, 12 MW leading load: efficiency, zero regulation
Short answer
Efficiency is 92.45%. To make voltage regulation zero, add about 0.2 MVAr of shunt capacitance at the load, resulting in a net receiving-end power factor of approximately 0.894 leading.
A 50 Hz, 3-phase, 33 kV overhead line is supplying a load of 12 MW at 0.9 p.f. leading. The line has a series impedance of 6 + j16 Ω/phase. Compute the efficiency of the transmission line. How can the voltage regulation of the line be made zero?
Short line: , = 33 kV, load 12 MW at 0.9 pf leading.
Efficiency
Present regulation
The regulation is already very small, because the leading load current nearly cancels the drop.
Making regulation zero
Zero regulation needs . With line kV, MW, MVAr:
The root nearer zero is
The load supplies MVAr, so a little more leading VAr is needed:
So connect a small shunt capacitor (about 0.2 MVAr, F per phase in star) at the receiving end, or raise the leading current of a synchronous load slightly. In general, regulation is made zero by adjusting receiving-end reactive power (capacitor or reactor) until the net pf is near leading.
Note: the approximate rule gives pf 0.936 lead here, but at such small regulation the neglected quadrature term matters, so the exact value above is used.
Answer: Efficiency ≈ 92.45 %. Regulation (now 0.26 %) becomes zero with about 0.2 MVAr of extra shunt capacitance at the load (net pf ≈ 0.894 leading).
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Zero regulation for 40 MW leading load · Power System Analysis I, chapter 6 · asked 2×
- 33 kV, 15 MW line: efficiency and regulation · Power System Analysis I, chapter 6
- Efficiency at 0.995 leading pf and zero regulation · Power System Analysis I, chapter 6
- 12 km 33 kV line: losses, zero-regulation capacitor · Power System Analysis I, chapter 6
- Capacitor for zero regulation, 70 km 220 kV line · Power System Analysis I, chapter 6
- 12 km line at 32.5 kV: regulation and capacitor · Power System Analysis I, chapter 6
- Regulation and efficiency of 100 km, 110 kV line · Power System Analysis I, chapter 6 · asked 2×
- 220 kV double circuit efficiency and regulation · Transmission and Distribution System Design, chapter 4
- Conductor selection, 100 MW 70 km 132 kV · Transmission and Distribution System Design, chapter 4
- Peterson coil for 33 kV 60 km line · Switchgear and Protection, chapter 5 · asked 6×
- Currents and efficiency of 132/11 kV transformer at 5 MW · Electrical Machines I, chapter 2 · asked 3×